-9-
Released 2018-01-12
Drawing No. LP0932
REMOTE INPUT
:
Input:
Program selectable 0-5 V, 1-5 V, 0-10 V, 0-20 mA, 4-20 mA
A/D Conversion Rate
: 10 samples per second
INPUT RANGE
ACCURACY
@ 0 to 50 °C
INPUT
IMPEDANCE
MAX
OVERLOAD
0-5 VDC
0.3% of rdg
+ 0.03 V
200 K
W
30 V
1-5 VDC
0.3% of rdg
+ 0.03 V
200 K
W
30 V
0-10 VDC
0.3% of rdg
+ 0.03 V
200 K
W
30 V
0-20 mA
0.3% of rdg
+ 0.04 mA
249
W
30 mA
4-20 mA
0.3% of rdg
+ 0.04 mA
249
W
30 mA
9.
USER INPUT
: (Optional)
Contact Input
: ON Resistance 1 K
W
max.
OFF Resistance 100 K
W
min.
Response Time
: 1 sec max
Functions
: Programmable
10.
MEMORY
: Nonvolatile E
2
PROM retains all programmable parameters.
11.
OUTPUT CAPABILITIES:
Output
: Time proportioning or DC Analog
Control
: PID, On/Off or user/manual
Cycle Time
: Programmable
Auto-Tune
: When selected, sets proportional band, integral time,
derivative time, and integration default. Also sets relative gain (if
applicable).
Input Fail Action
: Programmable output power level
CONTROL RELAY OUTPUTS (OUT1/OUT2)
:
Type:
Form A
Contact Rating:
5 A @ 250 VAC
Life Expectancy:
100,000 cycles at max. load rating
(Decreasing load and/or increasing cycle time, increases life
expectancy)
CONTROL SSR DRIVE OUTPUT (OUT1)
:
Rating: 12 VDC ± 10% @ 40 mA max.
CONTROL ANALOG OUTPUT (OUT1)
:
Output
: Time proportioning or DC Analog
Analog Types
: 4 mA -0.5/+0.0 mA to 20 mA -0.0/+0.5 mA or
0 VDC -0.0/+0.0 VDC to 10 VDC -0.0/+0.5 VDC
Isolation To Sensor & Communication Common
: 500 VDC for
1 min.
Resolution
: 12 bit
Compliance
: 10 VDC: 1 K
W
load min., 20 mA: 500
W
load max.
12.
ALARMS
: 2 relay alarm outputs.
Type:
Form A or Form C, model and alarm dependent
Contact Rating:
3 A @ 250 VAC
Life Expectancy:
100,000 cycles at max. load rating
(Decreasing load and/or increasing cycle time, increases life
expectancy)
Modes
:
None
Absolute High Acting (Balanced or Unbalanced Hysteresis)
Absolute Low Acting (Balanced or Unbalanced Hysteresis)
Deviation High Acting
Deviation Low Acting
Inside Band Acting
Outside Band Acting
Profile Error Band Timeout
Heater Current Alarm
Profile in Hold Mode
Profile is ramping up
Profile is ramping down
Profile is running
Profile is Paused
Profile is stopped
Profile has ended
Reset Action
: Programmable; automatic or latched
Standby Mode
: Programmable; yes or no
Hysteresis
: Programmable
Input Fail Response
: Programmable
Annunciator
: ALM1, ALM2, and ALM3, programmable for normal or
reverse acting
13.
ANALOG OUTPUT [RETRANS]
(Optional): Assignable to Input,
Setpoint, or Output Power.
Resolution
: 12 bit
Accuracy
: 4 mA -0.5/+0.0 mA to 20 mA -0.0/+0.5mA.
Compliance
: 500 Ohm load max.
14.
ISOLATION LEVEL
:
AC power with respect to all other I/O
: 250 V working (2300 V for 1
minute)
Sensor input to analog output
: 50 V working (500 V for 1 minute)
Relay contacts to all other I/O
: 250 V working (2300 V for 1 minute)
DC power with respect to sensor input and analog output
: 50 V
working (500 V for 1 minute)
15.
CERTIFICATIONS AND COMPLIANCES
:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
EN 61010-1
RoHS Compliant
UL Listed: File #E179259
IP65 Enclosure rating (Face only)
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
16.
ENVIRONMENTAL CONDITIONS
:
Operating Temperature Range
: 0 to 50 °C
Storage Temperature Range
: -20 to 65 °C
Operating and Storage Humidity
: 80% max relative humidity (non-
condensing) from 0 °C to 50 °C
Vibration Resistance
: Operational 10 to 55 Hz, 1 g
Shock Resistance
: Operational 30 g
Altitude
: Up to 2000 meters
17.
CONNECTION
: Wire-clamping screw terminals
18.
CONSTRUCTION
: Black plastic alloy case and panel latch. Black
plastic textured bezel with transparent display window. Controller
meets IP65 requirements for indoor use when properly installed.
Installation Category II, Pollution Degree 2.
19.
WEIGHT
:
1/16 DIN: 5.3 oz (150 g)
1/8 DIN: 7.8 oz (221 g)
1/4 DIN: 11.0 oz (312 g)