background image

4

WIRING OVERVIEW

Electrical connections are made via screw-clamp terminals located on the

back of the meter. All conductors should conform to the meter’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that the power
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.

When wiring the meter, compare the numbers embossed on the back of the

meter case against those shown in wiring drawings for proper wire position.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded
wires should be tinned with solder.) Insert the lead under the correct screw-
clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).

EMC INSTALLATION GUIDELINES

Although this meter is designed with a high degree of immunity to Electro-

Magnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, source or coupling method into the meter may be different for various
installations. The meter becomes more immune to EMI with fewer I/O
connections. Cable length, routing, and shield termination are very important
and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.

1. The meter should be mounted in a metal enclosure, which is properly

connected to protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the meter and leave the other end of the

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far away as

possible from contactors, control relays, transformers, and other noisy
components.

5. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC# FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC# LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3

Note: Reference manufacturer’s instructions when installing a line filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

7. Switching of inductive loads produces high EMI. Use of snubbers across

inductive loads suppresses EMI. 

Snubber: RLC# SNUB0000.

4.0 WIRING THE METER

3.0 INSTALLING PLUG-IN CARDS

The Plug-in cards are separately purchased optional cards that perform

specific functions. These cards plug into the main circuit board of the meter. The
Plug-in cards have many unique functions when used with the PAXR. The
literature that comes with these cards should be discarded, unless it specifically
states in the Plug-in Card literature that the information applies to the PAXR.

CAUTION

: The Plug-in card and main circuit board contain static

sensitive components. Before handling the cards, discharge static
charges from your body by touching a grounded bare metal
object. Ideally, handle the cards at a static controlled clean
workstation. Also, only handle the cards by the edges. Dirt, oil or
other contaminants that may contact the cards can adversely
affect circuit operation.

To Install:

1. With the case open, locate the Setpoint Plug-in card connector for the card to

be installed. When installing the card, hold the meter by the rear terminals
and not by the front display board.*

2. Install the Plug-in card by aligning the card terminals with the slot bay in the

rear cover. Be sure the connector is fully engaged and the tab on the Plug-in
card rests in the alignment slot on the display board.

3. Slide the meter base back into the case. Be sure the rear cover latches fully

into the case.

4. Apply the Plug-in card label to the bottom side of the meter. Do Not Cover

the vents on the top surface of the meter. The surface of the case must be
clean for the label to adhere properly. Apply the label to the area designated
by the large case label.

TOP VIEW

Quad Sourcing Open Collector Output Card Supply Select

* If installing the Quad sourcing Plug-in Card (PAXCDS40), set the
jumper for internal or external supply operation before continuing.

Summary of Contents for PAXR

Page 1: ...uctions that appear in this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a...

Page 2: ...20 msec Quad Sourcing Open Collector Card Type Four isolated sinking PNP transistors Isolation To Sensor User Input Commons 500 Vrms for 1 min Working Voltage 50 V Not isolated from all other commons...

Page 3: ...r Isolated quad sourcing PNP open collector The card can be installed initially or at a later date Each optional plug in card is shipped with complete installation instructions however programming sho...

Page 4: ...possible from contactors control relays transformers and other noisy components 5 In extremely high EMI environments the use of external EMI suppression devices such as ferrite suppression cores is ef...

Page 5: ...tween the appropriate User Input terminal and User Comm 4 3 INPUT WIRING CAUTION Sensor input common is NOT isolated from user input common In order to preserve the safety of the meter application the...

Page 6: ...xt parameter F1 Function key 1 hold for 3 seconds for Second Function 1 Increment selected parameter value or selections F2 Function key 2 hold for 3 seconds for Second Function 2 Decrement selected p...

Page 7: ...s may be completely restored in Module 9 This is a good starting point for programming problems Most parameters can be left at their Factory Settings without affecting basic start up These parameters...

Page 8: ...Y DESCRIPTION DISPLAY NO Minimum LO NO Maximum HI FACTORY DESCRIPTION DISPLAY DISPLAY DESCRIPTION FACTORY SP 1 Setpoint 1 NO SP 2 Setpoint 2 NO SP 3 Setpoint 3 NO SP 4 Setpoint 4 NO NO Setpoint 4 SP 4...

Page 9: ...grammed for 5 or The setpoint displays can be programmed for 5 or See the following table Accessible only with the Setpoint Plug in card installed Entry of a non zero value will cause the prompt 5 to...

Page 10: ...o function independent of being displayed MAXIMUM CAPTURE DELAY TIME 210 3 010 to 1 seconds When the Rate value is below the present Minimum rate value for the entered amount of time the meter will ca...

Page 11: ...hour is entered by a third less 1200 then Input value is a third less of of pulses per unit The same is true if the Input value is raised or lowered then Display value must be raised or lowered by the...

Page 12: ...e display will default to Select the next setpoint to be programmed and continue the sequence for each setpoint Pressing PAR at will exit Module 6 7 3 SETPOINT OUTPUT LOGIC Normal turns the output on...

Page 13: ...OPERATION Selecting 6 will disable low acting setpoints at a power up until the display value crosses into the alarm off area Once in the alarm off area the setpoint will function according to the con...

Page 14: ...urns to 5 0 Press DSP key to return to the Display Mode This will overwrite all user settings with the factory settings Pressing the PAR and DSP keys at the same time on power up will load the factory...

Page 15: ...OUT CHECK Active lock out user input ENTER Security code requested CERTAIN DISPLAYS ARE LOCKED OUT CHECK Module 3 programming INCORRECT DISPLAY VALUE CHECK Input wiring DIP switch setting input progr...

Page 16: ...ng Display Rate Scaling Input Rate Display Rounding Min Low Cut out 3 Max Capture Delay Time 3 Min Capture Delay Time 3333 3 B 3 7 3 7 3 5 3 3 53 Setpoint Select Setpoint Annunciators Output Logic Pow...

Reviews: