background image

11

RATE DISPLAY EXCEEDED

If the rate of the input signal causes a display that exceeds the capacity of the

Rate display (5 digits, 99999), then the display will indicate an overflow
condition by showing “

! *#*#

”. During this overflow condition, the Minimum

and Maximum rate values will stay at their values even during resets.

RATE SCALING

To scale the Rate, enter a Scaling Display value with a corresponding Scaling

Input value. (The Display and Input values can be entered by Key-in or Applied
Methods.) These values are internally plotted to a Display value of 0 and Input
value of 0 Hz. A linear relationship is formed between these points to yield a
rate display value that corresponds to the incoming input signal rate. The PAXR
is capable of showing a rate display value for any linear process.

KEY-IN SCALING METHOD CALCULATION

If a display value versus input signal (in pulses per second) is known, then

those values can be entered into Scaling Display (

!%&+$,

) and Scaling Input

(

!%&'(,

). No further calculations are needed.

If only the number of pulses per ‘single’ unit (i.e. # of pulses per foot) is

known, then it can be entered as the Scaling Input value and the Scaling Display
value will be entered as the following:

NOTES

:

1. If # of pulse per unit is less than 10, then multiply both Input and Display

values by 10.

2. If # of pulse per unit is less than 1, then multiply both Input and Display

values by 100.

3. If the Display value is raised or lowered, then Input value must be raised

or lowered by the same proportion (i.e. Display value for per hour is
entered by a third less (1200) then Input value is a third less of # of pulses
per unit). The same is true if the Input value is raised or lowered, then
Display value must be raised or lowered by the same proportion. 

4. Both values must be greater than 0.0.

EXAMPLE:

1. With 15.1 pulses per foot, show feet per minute in tenths. Scaling Display

= 60.0 Scaling Input = 15.1.

2. With 0.25 pulses per gallon, show whole gallons per hour. (To have greater

accuracy, multiply both Input and Display values by 10.) Scaling Display
= 36000 Scaling Input = 2.5

RATE PER

DISPLAY (

!%&+$,

)

INPUT (

!%&'(,

)

Second

1

# of pulses per unit

Minute

60

# of pulses per unit

Hour

3600

# of pulses per unit

INPUT FREQUENCY CALCULATION

The meter determines the input frequency by summing the

number of falling edges received during a sample period of
time. The sample period begins on the first falling edge. At this
falling edge, the meter starts accumulating time towards Low
Update and High Update values. Also, the meter starts
accumulating the number of falling edges. When the time
reaches the Low Update Time value, the meter looks for one
more falling edge to end the sample period. If a falling edge
occurs (before the High Update Time value is reached), the Rate
display will update to the new value and the next sample period
will start on the same edge. If the High Update Time value is
reached (without receiving a falling edge after reaching Low
Update Time), then the sample period will end but the Rate
display will be forced to zero. The High Update Time value
must be greater than the Low Update Time value. Both values
must be greater than 0.0. The input frequency calculated during
the sample period, is then shown as a Rate value determined by
either scaling method.

Summary of Contents for PAXR

Page 1: ...uctions that appear in this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a...

Page 2: ...20 msec Quad Sourcing Open Collector Card Type Four isolated sinking PNP transistors Isolation To Sensor User Input Commons 500 Vrms for 1 min Working Voltage 50 V Not isolated from all other commons...

Page 3: ...r Isolated quad sourcing PNP open collector The card can be installed initially or at a later date Each optional plug in card is shipped with complete installation instructions however programming sho...

Page 4: ...possible from contactors control relays transformers and other noisy components 5 In extremely high EMI environments the use of external EMI suppression devices such as ferrite suppression cores is ef...

Page 5: ...tween the appropriate User Input terminal and User Comm 4 3 INPUT WIRING CAUTION Sensor input common is NOT isolated from user input common In order to preserve the safety of the meter application the...

Page 6: ...xt parameter F1 Function key 1 hold for 3 seconds for Second Function 1 Increment selected parameter value or selections F2 Function key 2 hold for 3 seconds for Second Function 2 Decrement selected p...

Page 7: ...s may be completely restored in Module 9 This is a good starting point for programming problems Most parameters can be left at their Factory Settings without affecting basic start up These parameters...

Page 8: ...Y DESCRIPTION DISPLAY NO Minimum LO NO Maximum HI FACTORY DESCRIPTION DISPLAY DISPLAY DESCRIPTION FACTORY SP 1 Setpoint 1 NO SP 2 Setpoint 2 NO SP 3 Setpoint 3 NO SP 4 Setpoint 4 NO NO Setpoint 4 SP 4...

Page 9: ...grammed for 5 or The setpoint displays can be programmed for 5 or See the following table Accessible only with the Setpoint Plug in card installed Entry of a non zero value will cause the prompt 5 to...

Page 10: ...o function independent of being displayed MAXIMUM CAPTURE DELAY TIME 210 3 010 to 1 seconds When the Rate value is below the present Minimum rate value for the entered amount of time the meter will ca...

Page 11: ...hour is entered by a third less 1200 then Input value is a third less of of pulses per unit The same is true if the Input value is raised or lowered then Display value must be raised or lowered by the...

Page 12: ...e display will default to Select the next setpoint to be programmed and continue the sequence for each setpoint Pressing PAR at will exit Module 6 7 3 SETPOINT OUTPUT LOGIC Normal turns the output on...

Page 13: ...OPERATION Selecting 6 will disable low acting setpoints at a power up until the display value crosses into the alarm off area Once in the alarm off area the setpoint will function according to the con...

Page 14: ...urns to 5 0 Press DSP key to return to the Display Mode This will overwrite all user settings with the factory settings Pressing the PAR and DSP keys at the same time on power up will load the factory...

Page 15: ...OUT CHECK Active lock out user input ENTER Security code requested CERTAIN DISPLAYS ARE LOCKED OUT CHECK Module 3 programming INCORRECT DISPLAY VALUE CHECK Input wiring DIP switch setting input progr...

Page 16: ...ng Display Rate Scaling Input Rate Display Rounding Min Low Cut out 3 Max Capture Delay Time 3 Min Capture Delay Time 3333 3 B 3 7 3 7 3 5 3 3 53 Setpoint Select Setpoint Annunciators Output Logic Pow...

Reviews: