red lion PAXDP User Manual Download Page 6

WIRING OVERVIEW

Electrical connections are made via screw-clamp terminals located on the 

back of the meter. All conductors should conform to the meter’s voltage and 

current ratings. All cabling should conform to appropriate standards of good 

installation, local codes and regulations. It is recommended that power supplied 

to the meter (DC or AC) be protected by a fuse or circuit breaker.

When wiring the meter, compare the numbers embossed on the back of the 

meter case against those shown in wiring drawings for proper wire position. 

Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded 

wires should be tinned with solder). Insert the lead under the correct screw-

clamp terminal and tighten until the wire is secure. (Pull wire to verify 

tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two 

#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).

EMC INSTALLATION GUIDELINES

Although this meter is designed with a high degree of immunity to Electro-

Magnetic Interference (EMI), proper installation and wiring methods must be 

followed to ensure compatibility in each application. The type of the electrical 

noise, its source or the method of coupling into the unit may be different for 

various installations. Listed below are some EMC guidelines for successful 

installation in an industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly 

connected to protective earth.

2. With use of the lower input ranges or signal sources with high source 

impedance, the use of shielded cable may be necessary. This helps to guard 

against stray AC pick-up. Attach the shield to the input common of the meter. 

3. To minimize potential noise problems, power the meter from the same power 

branch, or at least the same phase voltage as that of the signal source.

4. Never run Signal or Control cables in the same conduit or raceway with AC 

power lines, conductors feeding motors, solenoids, SCR controls, and 

heaters, etc. The cables should be run in metal conduit that is properly 

grounded. This is especially useful in applications where cable runs are long 

and portable two-way radios are used in close proximity or if the installation 

is near a commercial radio transmitter.

5. Signal or Control cables within an enclosure should be routed as far away as 

possible from contactors, control relays, transformers, and other noisy 

components.

6. In extremely high EMI environments, the use of external EMI suppression 

devices, such as ferrite suppression cores, is effective. Install them on Signal 

and Control cables as close to the unit as possible. Loop the cable through the 

core several times or use multiple cores on each cable for additional protection. 

Install line filters on the power input cable to the unit to suppress power line 

interference. Install them near the power entry point of the enclosure. The 

following EMI suppression devices (or equivalent) are recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)

TDK # ZCAT3035-1330A

Steward #28B2029-0A0

Line Filters for input power cables:

Schaffner # FN2010-1/07 (RLC #LFIL0000)

Schaffner # FN670-1.8/07

Corcom #1VR3

Note: Reference manufacturer’s instructions when installing a line filter.

7. Long cable runs are more susceptible to EMI pickup than short cable runs. 

Therefore, keep cable runs as short as possible.

8. Switching of inductive loads produces high EMI. Use of snubbers across 

inductive loads suppresses EMI.

Snubber: RLC#SNUB0000.

4.0 W

iring

 

The

 m

eTer

6

The plug-in cards are separately purchased optional cards that perform 

specific functions. These cards plug into the main circuit board of the meter. The 

plug-in cards have many unique functions when used with the PAX. 

  

CAUTION

: The plug-in card and main circuit board contain static 

sensitive components. Before handling the cards, discharge static 

charges from your body by touching a grounded bare metal 

object. Ideally, handle the cards at a static controlled clean 

workstation. Also, only handle the cards by the edges. Dirt, oil or 

other contaminants that may contact the cards can adversely 

affect circuit operation.

To Install:

1. With the meter removed from the case, locate the plug-in card connector for 

the card type to be installed. The types are keyed by position with different 

main circuit board connector locations. When installing the card, hold the 

meter by the rear terminals and not by the front display board.

If installing the Quad sourcing Plug-in Card (PAXCDS40), set the jumper for 

internal or external supply operation before continuing. 

2. Install the plug-in card by aligning the card terminals with the slot bay in the 

rear cover. Be sure the connector is fully engaged and the tab on the plug-in 

card rests in the alignment slot on the display board.

3. Slide the meter base back into the case. Be sure the rear cover latches fully 

into the case.

4. Apply the plug-in card label to the bottom side of the meter in the designated 

area. Do Not Cover the vents on the top surface of the meter. The surface of 

the case must be clean for the label to adhere properly.

Internal Supply

(18 V unregulated)

External Supply

(30 V       )

 max

3.0 i

nsTalling

 p

lug

-i

n

 C

ards

Finger

Tab

Finger

Tab

Serial

Communications

Card

Setpoint

Output

Card

Alignment

Slots

Connectors

Analog Output

Card

Main

Circuit

Board

TOP VIEW

Summary of Contents for PAXDP

Page 1: ...eadout of totalized flow calculate service intervals of motors or pumps etc The totalizer can also accumulate batch operations The meter has four setpoint outputs implemented on Plug in option cards T...

Page 2: ...S30 Quad Setpoint Sourcing Open Collector Output Card PAXCDS40 PAXCDC RS485 Serial Communications Card with Terminal Block PAXCDC10 Extended RS485 Serial Communications Card with Dual RJ11 Connector P...

Page 3: ...Response Time 20 msec max Logic State Jumper selectable for sink source logic 12 TOTALIZER Function Time Base second minute hour or day Batch Can accumulate gate input display from a user input Time...

Page 4: ...lude PAXCDS10 Dual Relay FORM C Normally open closed PAXCDS20 Quad Relay FORM A Normally open only PAXCDS30 Isolated quad sinking NPN open collector PAXCDS40 Isolated quad sourcing PNP open collector...

Page 5: ...rature and provides good air circulation Placing the unit near devices that generate excessive heat should be avoided The bezel should be cleaned only with a soft cloth and neutral soap product Do NOT...

Page 6: ...to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppres...

Page 7: ...In order to preserve the safety of the meter application the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must be at protective earth gro...

Page 8: ...device between appropriate User Input terminal and User Comm DSP 8 8 8 8 8 A C B PAR F1 F2 RST A 1 S P S P S 2 3 P P4 S Display Readout Legends Optional Custom Units Overlay Setpoint Alarm Annunciato...

Page 9: ...listed on the Parameter Value Chart following the programming section ALTERNATING SELECTION DISPLAY In the module description sections which follow the dual display with arrows appears for each progra...

Page 10: ...less than the band value the filter engages again This allows for a stable readout but permits the display to settle rapidly after a large process change The value of the band is in display units ind...

Page 11: ...mA 0 with 20 mA the desired high Display Value The calculations stop at the limits of the Input Range Jumper position 6 For input levels beyond the last programmed Input Value the meter extends the D...

Page 12: ...B Display will normally show the Relative unless switched by this function The Absolute is a gross value based on Module 1 DSP and INP entries without the Display Offset Value The Absolute display is...

Page 13: ...ECTIONS Select main or alternate setpoints Reset Setpoint 1 Alarm 1 Reset Setpoint 2 Alarm 2 Reset Setpoint 3 Alarm 3 Reset Setpoint 4 Alarm 4 Reset Setpoint 3 4 Alarm 3 4 Reset Setpoint 2 3 4 Alarm 2...

Page 14: ...s to be viewed and modified This Programming Mode can be locked with a security code and or user input When locked and the PAR key is pressed the meter enters a Quick Programming Mode In this mode the...

Page 15: ...present MAX value for the entered delay time the meter will capture that display value as the new MAX reading A delay time helps to avoid false captures of sudden short spikes to sec MAX CAPTURE ASSIG...

Page 16: ...ut permits the display to settle rapidly after a large process change The value of the band is in display units independent of the Display Decimal Point position A band setting of 0 keeps the digital...

Page 17: ...Totalizer Decimal Point parameter TOTALIZER HIGH ORDER DISPLAY When the total exceeds 5 digits the front panel annunciator flashes if assigned to A B or C display In this case the meter continues to t...

Page 18: ...with unbalanced hysteresis Deviation high with unbalanced hysteresis Deviation low with unbalanced hysteresis Inside band with unbalanced hysteresis Outside band with unbalanced hysteresis Lower Total...

Page 19: ...0 0 allows the meter to update the alarm status per the response time listed in the Specifications When the output logic is this becomes on time delay Any time accumulated at power off resets during p...

Page 20: ...not be used The PAXCDC1 RS485 or PAXCDC2 RS232 card should be used instead COMMUNICATIONS TYPE RLC Protocol ASCII Modbus RTU Modbus ASCII The Communication Type factory settings must be changed from...

Page 21: ...udes read only registers then only the write registers will change 4 If the write value exceeds the register limit see Register Table then that register value changes to its high or low limit FC17 Rep...

Page 22: ...o word N A N A N A Read Only 40003 Input B Relative Value Hi word N A N A N A Read Only 40004 40005 40006 40007 40009 40011 40013 40017 40015 40019 40008 40010 40012 40014 40018 40016 40020 Calculatio...

Page 23: ...ess specifier the next character is the command character 3 The next character is the Register ID This identifies the register that the command affects The P command does not require a Register ID cha...

Page 24: ...ot change the corresponding output mode U abcde e Analog Output d SP4 c SP3 b SP2 a SP1 Example VU00011 places SP4 and Analog in manual Analog Output Register AOR ID W This register stores the present...

Page 25: ...RMAT Data is transferred from the meter through a serial communication channel In serial communications the voltage is switched between a high and low level at a predetermined rate baud rate using ASC...

Page 26: ...E ANALOG UPDATE TIME to to to Enter the source for the analog output to retransmit Relative net Input Value The Relative Input Value is the Absolute Input Value that includes the Display Offset Value...

Page 27: ...ve selections to be calibrated At each prompt use the PAX arrow keys to adjust the external meter display to match the selection being calibrated When the external reading matches or if this range is...

Page 28: ...K Power level power connections Module 3 programming NO DISPLAY REMEDIES PROBLEM For further assistance contact technical support at the appropriate company numbers listed PARAMETER VALUE CHART Progra...

Page 29: ...RE ASSIGNMENT CALCULATION CONSTANT VALUE CALCULATION FUNCTION MIN CAPTURE DELAY TIME INPUT B OFFSET VALUE MAX CAPTURE DELAY TIME INPUT A OFFSET VALUE CALCULATION FILTER BAND DISPLAY INTENSITY LEVEL US...

Page 30: ...SP t LO t LO AS HI AS HI t SCFAC ASIN dECPt dECPt tbASE Locut P uP PAr INP A CALC INP b tYPE dAtA bAUd SPNt HILO tot Addr dELAY YES Abru OPt NO RLC MODE ONLY ASn n Scaling Style FUNCTION KEYS USER INP...

Page 31: ...31 This page intentionally left blank...

Page 32: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Reviews: