red lion PAXDP User Manual Download Page 21





TRANSMIT DELAY

CRIMSON SOFTWARE

Following a transmit value (‘*’ terminator) or Modbus command, the 

PAXDP will wait this minimum amount of time in seconds before issuing a 

serial response.



 to 



When communicating with Crimson 2 software, the PAXDP must be set in 

default configuration type of: 

Communications Type: MODBUS RTU 

Baud Rate: 38400

Data Bit: 8

ParityBit: no

Meter Unit Address: 247 

SERIAL MODBUS COMMUNICATIONS

Modbus Communications requires that the Serial Communication Type 

Parameter (



) be set to “



” or “



”. 

SUPPORTED FUNCTION CODES

FC03: Read Holding Registers

1. Up to 32 registers can be requested at one time.

2. HEX <8000> is returned for non-used registers.

FC04: Read Input Registers

1. Up to 32 registers can be requested at one time.

2. Block starting point can not exceed register boundaries.

3. HEX <8000> is returned in registers beyond the boundaries.

4. Input registers are a mirror of Holding registers.

FC06: Preset Single Register

1. HEX <8001> is echoed back when attempting to write to a read only 

register.

2. If the write value exceeds the register limit (see Register Table), then that 

register value changes to its high or low limit. It is also returned in the 

response.

FC08: Diagnostics

The following is sent upon FC08 request:

Module Address, 08 (FC code), 04 (byte count), “Total Comms” 2 byte count,

“Total Good Comms” 2 byte count, checksum of the string

“Total Comms” is the total number of messages received that were addressed 

to the PAXDP. “Total Good Comms” is the total messages received by the 

PAXDP with good address, parity and checksum. Both counters are reset to 0 

upon response to FC08 and at power-up.

FC16: Preset Multiple Registers

1. No response is given with an attempt to write to more than 32 registers at 

a time.

2. Block starting point cannot exceed the read and write boundaries (40001-

41280).

3. If a multiple write includes read only registers, then only the write registers 

will change.

4. If the write value exceeds the register limit (see Register Table), then that 

register value changes to its high or low limit.

FC17: Report Slave ID

The following is sent upon FC17 request:

RLC-PAXDP ab<0100h><20h><20h><10h>

 

                                                   16 Guid/Scratch Pad

 

                                        Max Register Reads (32)

 

                               Max Register Writes (32)

 

                  Software Version Number

 

              b = Linear Card “0” = None, “1” = Yes

 

             a = SP Card, “0”-No SP, “2” or “4” SP

                    

a = “0”(none), “2”, “4” SP card installed 

b = “0”(none) or “1” Linear Card installed), 

SUPPORTED EXCEPTION CODES

01: Illegal Function

Issued whenever the requested function is not implemented in the meter.

02: Illegal Data Address

Issued whenever an attempt is made to access a single register that does not 

exist (outside the implemented space) or to access a block of registers that falls 

completely outside the implemented space.

03: Illegal Data Value

Issued when an attempt is made to read or write more registers than the meter 

can handle in one request.

07: Negative Acknowledge

Issued when a write to a register is attempted with an invalid string length.

21





ABBREVIATED PRINTING

Select 



 for full print or Command T transmissions (meter address, 

parameter data and mnemonics) or 



 for abbreviated print transmissions 

(parameter data only). This will affect all the parameters selected in the print 

options. (If the meter address is 00, it will not be sent during a full transmission.)





PRINT OPTIONS



 - Enters the sub-menu to select the meter parameters to appear during a 

print request. For each parameter in the sub-menu, select 



 for that parameter 

information to be sent during a print request or 



 for that parameter information 

not to be sent. A print request is sometimes referred to as a block print because 

more than one parameter information (meter address, parameter data and 

mnemonics) can be sent to a printer or computer as a block.

PARAMETER

DESCRIPTION

 

Input A Value

 

Input B Value



Calculation



Total Value



Max. & Min.



Setpoint Values





Parameters below only appear when communications type (



) parameter 

is set to 



.

Summary of Contents for PAXDP

Page 1: ...eadout of totalized flow calculate service intervals of motors or pumps etc The totalizer can also accumulate batch operations The meter has four setpoint outputs implemented on Plug in option cards T...

Page 2: ...S30 Quad Setpoint Sourcing Open Collector Output Card PAXCDS40 PAXCDC RS485 Serial Communications Card with Terminal Block PAXCDC10 Extended RS485 Serial Communications Card with Dual RJ11 Connector P...

Page 3: ...Response Time 20 msec max Logic State Jumper selectable for sink source logic 12 TOTALIZER Function Time Base second minute hour or day Batch Can accumulate gate input display from a user input Time...

Page 4: ...lude PAXCDS10 Dual Relay FORM C Normally open closed PAXCDS20 Quad Relay FORM A Normally open only PAXCDS30 Isolated quad sinking NPN open collector PAXCDS40 Isolated quad sourcing PNP open collector...

Page 5: ...rature and provides good air circulation Placing the unit near devices that generate excessive heat should be avoided The bezel should be cleaned only with a soft cloth and neutral soap product Do NOT...

Page 6: ...to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppres...

Page 7: ...In order to preserve the safety of the meter application the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must be at protective earth gro...

Page 8: ...device between appropriate User Input terminal and User Comm DSP 8 8 8 8 8 A C B PAR F1 F2 RST A 1 S P S P S 2 3 P P4 S Display Readout Legends Optional Custom Units Overlay Setpoint Alarm Annunciato...

Page 9: ...listed on the Parameter Value Chart following the programming section ALTERNATING SELECTION DISPLAY In the module description sections which follow the dual display with arrows appears for each progra...

Page 10: ...less than the band value the filter engages again This allows for a stable readout but permits the display to settle rapidly after a large process change The value of the band is in display units ind...

Page 11: ...mA 0 with 20 mA the desired high Display Value The calculations stop at the limits of the Input Range Jumper position 6 For input levels beyond the last programmed Input Value the meter extends the D...

Page 12: ...B Display will normally show the Relative unless switched by this function The Absolute is a gross value based on Module 1 DSP and INP entries without the Display Offset Value The Absolute display is...

Page 13: ...ECTIONS Select main or alternate setpoints Reset Setpoint 1 Alarm 1 Reset Setpoint 2 Alarm 2 Reset Setpoint 3 Alarm 3 Reset Setpoint 4 Alarm 4 Reset Setpoint 3 4 Alarm 3 4 Reset Setpoint 2 3 4 Alarm 2...

Page 14: ...s to be viewed and modified This Programming Mode can be locked with a security code and or user input When locked and the PAR key is pressed the meter enters a Quick Programming Mode In this mode the...

Page 15: ...present MAX value for the entered delay time the meter will capture that display value as the new MAX reading A delay time helps to avoid false captures of sudden short spikes to sec MAX CAPTURE ASSIG...

Page 16: ...ut permits the display to settle rapidly after a large process change The value of the band is in display units independent of the Display Decimal Point position A band setting of 0 keeps the digital...

Page 17: ...Totalizer Decimal Point parameter TOTALIZER HIGH ORDER DISPLAY When the total exceeds 5 digits the front panel annunciator flashes if assigned to A B or C display In this case the meter continues to t...

Page 18: ...with unbalanced hysteresis Deviation high with unbalanced hysteresis Deviation low with unbalanced hysteresis Inside band with unbalanced hysteresis Outside band with unbalanced hysteresis Lower Total...

Page 19: ...0 0 allows the meter to update the alarm status per the response time listed in the Specifications When the output logic is this becomes on time delay Any time accumulated at power off resets during p...

Page 20: ...not be used The PAXCDC1 RS485 or PAXCDC2 RS232 card should be used instead COMMUNICATIONS TYPE RLC Protocol ASCII Modbus RTU Modbus ASCII The Communication Type factory settings must be changed from...

Page 21: ...udes read only registers then only the write registers will change 4 If the write value exceeds the register limit see Register Table then that register value changes to its high or low limit FC17 Rep...

Page 22: ...o word N A N A N A Read Only 40003 Input B Relative Value Hi word N A N A N A Read Only 40004 40005 40006 40007 40009 40011 40013 40017 40015 40019 40008 40010 40012 40014 40018 40016 40020 Calculatio...

Page 23: ...ess specifier the next character is the command character 3 The next character is the Register ID This identifies the register that the command affects The P command does not require a Register ID cha...

Page 24: ...ot change the corresponding output mode U abcde e Analog Output d SP4 c SP3 b SP2 a SP1 Example VU00011 places SP4 and Analog in manual Analog Output Register AOR ID W This register stores the present...

Page 25: ...RMAT Data is transferred from the meter through a serial communication channel In serial communications the voltage is switched between a high and low level at a predetermined rate baud rate using ASC...

Page 26: ...E ANALOG UPDATE TIME to to to Enter the source for the analog output to retransmit Relative net Input Value The Relative Input Value is the Absolute Input Value that includes the Display Offset Value...

Page 27: ...ve selections to be calibrated At each prompt use the PAX arrow keys to adjust the external meter display to match the selection being calibrated When the external reading matches or if this range is...

Page 28: ...K Power level power connections Module 3 programming NO DISPLAY REMEDIES PROBLEM For further assistance contact technical support at the appropriate company numbers listed PARAMETER VALUE CHART Progra...

Page 29: ...RE ASSIGNMENT CALCULATION CONSTANT VALUE CALCULATION FUNCTION MIN CAPTURE DELAY TIME INPUT B OFFSET VALUE MAX CAPTURE DELAY TIME INPUT A OFFSET VALUE CALCULATION FILTER BAND DISPLAY INTENSITY LEVEL US...

Page 30: ...SP t LO t LO AS HI AS HI t SCFAC ASIN dECPt dECPt tbASE Locut P uP PAr INP A CALC INP b tYPE dAtA bAUd SPNt HILO tot Addr dELAY YES Abru OPt NO RLC MODE ONLY ASn n Scaling Style FUNCTION KEYS USER INP...

Page 31: ...31 This page intentionally left blank...

Page 32: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Reviews: