red lion PAXDP User Manual Download Page 20

20





BAUD RATE

Set the baud rate to match the other serial communications equipment on the 

serial link. Normally, the baud rate is set to the highest value that all the serial 

equipment are capable of transmitting and receiving.



DATA BIT

Select either 7 or 8 bit data word lengths. Set the word length to match the 

other serial communications equipment on the serial link.





PARITY BIT

Set the parity bit to match that of the other serial communications equipment 

on the serial link. The meter ignores the parity when receiving data and sets the 

parity bit for outgoing data. If no parity is selected with 7 bit word length, an 

additional stop bit is used to force the frame size to 10 bits.





METER UNIT ADDRESS

Enter the serial meter (node) address. The address range is dependent on the 



 parameter. With a single unit, configured for RLC protocol (



 =

 



), an address is not needed and a value of zero can be used. With multiple 

units (RS485 applications), a unique 2 digit address number must be assigned 

to each meter.

7-SrL

bAUd

tYPE

dAtA

dELAY

INP A

PAR

Communications 

Type

Baud Rate

Transmit 

Delay

PAr

Addr

Meter

 Address

INP b

Parity Bit

Data Bit

Pro

Print Setpoint

Values

Print 

Input B

CALC

Print

Max/Min

Print 

Calculation 

tot

HILO

Print

Total

SPNt

Print 

Input A

Print 

Options

OPt

Abbreviated 

Printing

Abru

RLC MODE ONLY

NO

YES

PARAMETER MENU

























 to 

 

(RLC Protocol)

 to 

  

(Modbus)

Select the desired communications protocol. Modbus is preferred as it 

provides access to all meter values and parameters. Since the Modbus protocol 

is included within the PAXDP, the PAX Modbus option card, PAXCDC4, 

should not be used. The PAXCDC1 (RS485), or PAXCDC2 (RS232) card 

should be used instead.

COMMUNICATIONS TYPE



 

- RLC Protocol (ASCII)



 

- Modbus RTU

 †



 

- Modbus ASCII





 

 

The Communication Type factory settings must be changed from the 

Modbus RTU for Crimson 2 communications.





SETPOINT ANNUNCIATORS









The 



 mode disables display setpoint annunciators. The  



 mode 

displays the corresponding setpoint annunciators of “on” alarm outputs. The 



 mode  displays the corresponding setpoint annunciators of “off” alarms 

outputs. The 



 mode flashes the corresponding setpoint annunciators of 

“on” alarm outputs.

Alternate Setpoints

An Alternate list of setpoint values can be stored and recalled as needed. The 

Alternate list allows an additional set of setpoint values. (The setpoint numbers 

nor rear terminal numbers will change in the Alternate list.) The Alternate list 

can only be activated through a function key or user input programmed for 



 

in Module 2. When the Alternate list is selected, the Main list is stored and 

becomes inactive. When changing between Main and Alternate, the alarm state 

of Auto Reset Action alarms will always follow their new value. Latched “on” 

alarms will always stay latched during the transition and can only be reset with 

a user input or function key. Only during the function key or user input 

transition does the display indicate which list is being used.

Ñ

 - A communication card must be installed in order to access this 

module.

6.7 mOdule 7 - s

erial

 C

OmmuniCaTiOns

 p

arameTers

 (



Ñ

ALARM

STATE

OFF

ON

Hys

SP

OFF

ON

OFF

OFF

ON

OFF ON

OFF

OFF

ON

OFF

ON

OFF

MANUAL

RESET

SP - Hys

Auto

)

(

LAtC1

)

(

LAtC2

)

Setpoint Alarm Reset Actions

When 



, the alarm is disabled (after a power up) until the  trigger point is 

crossed. Once the alarm is on, the alarm operates normally per the Setpoint 

Action and Reset Mode.





STANDBY OPERATION





Summary of Contents for PAXDP

Page 1: ...eadout of totalized flow calculate service intervals of motors or pumps etc The totalizer can also accumulate batch operations The meter has four setpoint outputs implemented on Plug in option cards T...

Page 2: ...S30 Quad Setpoint Sourcing Open Collector Output Card PAXCDS40 PAXCDC RS485 Serial Communications Card with Terminal Block PAXCDC10 Extended RS485 Serial Communications Card with Dual RJ11 Connector P...

Page 3: ...Response Time 20 msec max Logic State Jumper selectable for sink source logic 12 TOTALIZER Function Time Base second minute hour or day Batch Can accumulate gate input display from a user input Time...

Page 4: ...lude PAXCDS10 Dual Relay FORM C Normally open closed PAXCDS20 Quad Relay FORM A Normally open only PAXCDS30 Isolated quad sinking NPN open collector PAXCDS40 Isolated quad sourcing PNP open collector...

Page 5: ...rature and provides good air circulation Placing the unit near devices that generate excessive heat should be avoided The bezel should be cleaned only with a soft cloth and neutral soap product Do NOT...

Page 6: ...to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppres...

Page 7: ...In order to preserve the safety of the meter application the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must be at protective earth gro...

Page 8: ...device between appropriate User Input terminal and User Comm DSP 8 8 8 8 8 A C B PAR F1 F2 RST A 1 S P S P S 2 3 P P4 S Display Readout Legends Optional Custom Units Overlay Setpoint Alarm Annunciato...

Page 9: ...listed on the Parameter Value Chart following the programming section ALTERNATING SELECTION DISPLAY In the module description sections which follow the dual display with arrows appears for each progra...

Page 10: ...less than the band value the filter engages again This allows for a stable readout but permits the display to settle rapidly after a large process change The value of the band is in display units ind...

Page 11: ...mA 0 with 20 mA the desired high Display Value The calculations stop at the limits of the Input Range Jumper position 6 For input levels beyond the last programmed Input Value the meter extends the D...

Page 12: ...B Display will normally show the Relative unless switched by this function The Absolute is a gross value based on Module 1 DSP and INP entries without the Display Offset Value The Absolute display is...

Page 13: ...ECTIONS Select main or alternate setpoints Reset Setpoint 1 Alarm 1 Reset Setpoint 2 Alarm 2 Reset Setpoint 3 Alarm 3 Reset Setpoint 4 Alarm 4 Reset Setpoint 3 4 Alarm 3 4 Reset Setpoint 2 3 4 Alarm 2...

Page 14: ...s to be viewed and modified This Programming Mode can be locked with a security code and or user input When locked and the PAR key is pressed the meter enters a Quick Programming Mode In this mode the...

Page 15: ...present MAX value for the entered delay time the meter will capture that display value as the new MAX reading A delay time helps to avoid false captures of sudden short spikes to sec MAX CAPTURE ASSIG...

Page 16: ...ut permits the display to settle rapidly after a large process change The value of the band is in display units independent of the Display Decimal Point position A band setting of 0 keeps the digital...

Page 17: ...Totalizer Decimal Point parameter TOTALIZER HIGH ORDER DISPLAY When the total exceeds 5 digits the front panel annunciator flashes if assigned to A B or C display In this case the meter continues to t...

Page 18: ...with unbalanced hysteresis Deviation high with unbalanced hysteresis Deviation low with unbalanced hysteresis Inside band with unbalanced hysteresis Outside band with unbalanced hysteresis Lower Total...

Page 19: ...0 0 allows the meter to update the alarm status per the response time listed in the Specifications When the output logic is this becomes on time delay Any time accumulated at power off resets during p...

Page 20: ...not be used The PAXCDC1 RS485 or PAXCDC2 RS232 card should be used instead COMMUNICATIONS TYPE RLC Protocol ASCII Modbus RTU Modbus ASCII The Communication Type factory settings must be changed from...

Page 21: ...udes read only registers then only the write registers will change 4 If the write value exceeds the register limit see Register Table then that register value changes to its high or low limit FC17 Rep...

Page 22: ...o word N A N A N A Read Only 40003 Input B Relative Value Hi word N A N A N A Read Only 40004 40005 40006 40007 40009 40011 40013 40017 40015 40019 40008 40010 40012 40014 40018 40016 40020 Calculatio...

Page 23: ...ess specifier the next character is the command character 3 The next character is the Register ID This identifies the register that the command affects The P command does not require a Register ID cha...

Page 24: ...ot change the corresponding output mode U abcde e Analog Output d SP4 c SP3 b SP2 a SP1 Example VU00011 places SP4 and Analog in manual Analog Output Register AOR ID W This register stores the present...

Page 25: ...RMAT Data is transferred from the meter through a serial communication channel In serial communications the voltage is switched between a high and low level at a predetermined rate baud rate using ASC...

Page 26: ...E ANALOG UPDATE TIME to to to Enter the source for the analog output to retransmit Relative net Input Value The Relative Input Value is the Absolute Input Value that includes the Display Offset Value...

Page 27: ...ve selections to be calibrated At each prompt use the PAX arrow keys to adjust the external meter display to match the selection being calibrated When the external reading matches or if this range is...

Page 28: ...K Power level power connections Module 3 programming NO DISPLAY REMEDIES PROBLEM For further assistance contact technical support at the appropriate company numbers listed PARAMETER VALUE CHART Progra...

Page 29: ...RE ASSIGNMENT CALCULATION CONSTANT VALUE CALCULATION FUNCTION MIN CAPTURE DELAY TIME INPUT B OFFSET VALUE MAX CAPTURE DELAY TIME INPUT A OFFSET VALUE CALCULATION FILTER BAND DISPLAY INTENSITY LEVEL US...

Page 30: ...SP t LO t LO AS HI AS HI t SCFAC ASIN dECPt dECPt tbASE Locut P uP PAr INP A CALC INP b tYPE dAtA bAUd SPNt HILO tot Addr dELAY YES Abru OPt NO RLC MODE ONLY ASn n Scaling Style FUNCTION KEYS USER INP...

Page 31: ...31 This page intentionally left blank...

Page 32: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Reviews: