red lion PAXDP User Manual Download Page 17

17

tbASE

dECPt

SCFAC

Locut

P-uP

Pro

Totalizer 

Decimal Point

Totalizer

Time Base

Totalizer

Scale Factor

Totalizer Low 

Cut Value

Totalizer Power 

Up Reset

dECPt

Totalizer 

Assignment

5-tOt

5-tOt

PAR

PAR

ASIN

6.5  mOdule 5 - T

OTalizer

 (i

nTegraTOr

) p

arameTers

 (



)

PARAMETER MENU





TOTALIZER DECIMAL POINT*

For most applications, this should match the decimal point position of the 

meter value selected in the totalizer assignment. If a different location is 

desired, refer to Totalizer Scale Factor. 













TOTALIZER TIME BASE

This is the time base used in Totalizer accumulations. If the Totalizer is being 

accumulated through a user input programmed for Batch, then this parameter 

does not apply.

 

-

 

seconds (÷ 1)

 

-

 

days (÷ 86400)

 

- minutes (÷ 60)

The totalizer accumulates (integrates) the relative Input value using one of 

two modes. The first is using a time base. This can be used to provide an 

indication of total flow, usage or consumption over time. The second is through 

a user input or function key programmed for Batch (one time add on demand). 

This can be used for weighing applications where accumulation is based on a 

completed event. If the Totalizer is not needed, its display can be locked-out and 

this module can be skipped during programming.





TOTALIZER ASSIGNMENT

This parameter determines which value is to be totalized.











TOTALIZER SCALE FACTOR*

For most applications, the Totalizer reflects the same decimal point location 

and engineering units as the assigned Input Display. In these cases, the Totalizer 

Scale Factor is 1.000. The Totalizer Scale Factor can be used to scale the 

Totalizer to a different value than the Input Display. Common possibilities are:

1. Changing decimal point location (example tenths to whole)

2. Average over a controlled time frame.

Details on calculating the scale factor are shown later. 

If the Totalizer is being accumulated through a user input programmed for 

Batch, then this parameter does not apply.



 

to

 



 

-

 

hours (÷ 3600)





TOTALIZER LOW CUT VALUE*



 

to

 



A low cut value disables Totalizer when the Input Display value falls below 

the value programmed.





TOTALIZER POWER UP RESET

Reset totalizer

Do not reset totalizer





The Totalizer can be reset to zero on each meter power-up by setting this 

parameter to reset.

The decimal point position is dependent on the selection made in the 

“Totalizer Decimal Point” parameter.

TOTALIZER HIGH ORDER DISPLAY

When the total exceeds 5 digits, the front panel annunciator flashes (if 

assigned to A, B, or C display). In this case, the meter continues to totalize up 

to a  9 digit value. The high order 4 digits and the low order 5 digits of the total 

are displayed alternately. The letter “

” denotes the high order display.

TOTALIZER BATCHING

The Totalizer Time Base and scale factor are overridden when a user input or 

function key is programmed for store batch (



). In this mode, when the user 

input or function key is activated, the Input Display reading is one time added 

to the Totalizer (batch). The Totalizer retains a running sum of each batch 

operation until the Totalizer is reset. This is useful in weighing operations, when 

the value to be added is not based on time but after a filling event.

TOTALIZER USING TIME BASE

 Totalizer accumulates as defined by:

Input Display x Totalizer Scale Factor

Totalizer Time Base

Where:

Input Display - the present input reading

Totalizer Scale Factor - 0.001 to 65.000 

Totalizer Time Base -  (the division factor of  



)

Example: The input reading is at a constant rate of 10.0 gallons per minute. The 

Totalizer is used to determine how many gallons in tenths has flowed. 

Because the Input Display and Totalizer are both in tenths of gallons, the 

Totalizer Scale Factor is 1. With gallons per minute, the Totalizer Time Base 

is minutes (60). By placing these values in the equation, the Totalizer will 

accumulate every second as follows: 
10.0 x 1.000 = 0.1667 gallons accumulate each second 

      60

This results in:

 10.0 gallons accumulate each minute

 600.0 gallons accumulate each hour

TOTALIZER SCALE FACTOR CALCULATION EXAMPLES

1. When changing the Totalizer Decimal Point (



) location from the 

Input Display Decimal Point (



), the required Totalizer Scale Factor is 

multiplied by a power of ten.

Example:  Input  (



) = 0.0          Input (



) = 0.00

Totalizer 



Scale 

Factor

Totalizer 



Scale 

Factor

0.00

10

0.000

10

0.0

1

0.00

1

0

.1

0.0

.1

x10

.01

0

.01

x100

.001

x10

.001

            (x = Totalizer display is round by tens or hundreds)

2. To obtain an average reading within a controlled time frame, the selected 

Totalizer Time Base is divided by the given time period expressed in the same 

timing units.

Example: Average flow rate per hour in a 4 hour period, the scale factor 

would be 0.250. To achieve a controlled time frame, connect an external timer 

to a user input programmed for 



. The timer will control the start (reset) 

and the stopping (hold) of the totalizer.

Summary of Contents for PAXDP

Page 1: ...eadout of totalized flow calculate service intervals of motors or pumps etc The totalizer can also accumulate batch operations The meter has four setpoint outputs implemented on Plug in option cards T...

Page 2: ...S30 Quad Setpoint Sourcing Open Collector Output Card PAXCDS40 PAXCDC RS485 Serial Communications Card with Terminal Block PAXCDC10 Extended RS485 Serial Communications Card with Dual RJ11 Connector P...

Page 3: ...Response Time 20 msec max Logic State Jumper selectable for sink source logic 12 TOTALIZER Function Time Base second minute hour or day Batch Can accumulate gate input display from a user input Time...

Page 4: ...lude PAXCDS10 Dual Relay FORM C Normally open closed PAXCDS20 Quad Relay FORM A Normally open only PAXCDS30 Isolated quad sinking NPN open collector PAXCDS40 Isolated quad sourcing PNP open collector...

Page 5: ...rature and provides good air circulation Placing the unit near devices that generate excessive heat should be avoided The bezel should be cleaned only with a soft cloth and neutral soap product Do NOT...

Page 6: ...to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppres...

Page 7: ...In order to preserve the safety of the meter application the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must be at protective earth gro...

Page 8: ...device between appropriate User Input terminal and User Comm DSP 8 8 8 8 8 A C B PAR F1 F2 RST A 1 S P S P S 2 3 P P4 S Display Readout Legends Optional Custom Units Overlay Setpoint Alarm Annunciato...

Page 9: ...listed on the Parameter Value Chart following the programming section ALTERNATING SELECTION DISPLAY In the module description sections which follow the dual display with arrows appears for each progra...

Page 10: ...less than the band value the filter engages again This allows for a stable readout but permits the display to settle rapidly after a large process change The value of the band is in display units ind...

Page 11: ...mA 0 with 20 mA the desired high Display Value The calculations stop at the limits of the Input Range Jumper position 6 For input levels beyond the last programmed Input Value the meter extends the D...

Page 12: ...B Display will normally show the Relative unless switched by this function The Absolute is a gross value based on Module 1 DSP and INP entries without the Display Offset Value The Absolute display is...

Page 13: ...ECTIONS Select main or alternate setpoints Reset Setpoint 1 Alarm 1 Reset Setpoint 2 Alarm 2 Reset Setpoint 3 Alarm 3 Reset Setpoint 4 Alarm 4 Reset Setpoint 3 4 Alarm 3 4 Reset Setpoint 2 3 4 Alarm 2...

Page 14: ...s to be viewed and modified This Programming Mode can be locked with a security code and or user input When locked and the PAR key is pressed the meter enters a Quick Programming Mode In this mode the...

Page 15: ...present MAX value for the entered delay time the meter will capture that display value as the new MAX reading A delay time helps to avoid false captures of sudden short spikes to sec MAX CAPTURE ASSIG...

Page 16: ...ut permits the display to settle rapidly after a large process change The value of the band is in display units independent of the Display Decimal Point position A band setting of 0 keeps the digital...

Page 17: ...Totalizer Decimal Point parameter TOTALIZER HIGH ORDER DISPLAY When the total exceeds 5 digits the front panel annunciator flashes if assigned to A B or C display In this case the meter continues to t...

Page 18: ...with unbalanced hysteresis Deviation high with unbalanced hysteresis Deviation low with unbalanced hysteresis Inside band with unbalanced hysteresis Outside band with unbalanced hysteresis Lower Total...

Page 19: ...0 0 allows the meter to update the alarm status per the response time listed in the Specifications When the output logic is this becomes on time delay Any time accumulated at power off resets during p...

Page 20: ...not be used The PAXCDC1 RS485 or PAXCDC2 RS232 card should be used instead COMMUNICATIONS TYPE RLC Protocol ASCII Modbus RTU Modbus ASCII The Communication Type factory settings must be changed from...

Page 21: ...udes read only registers then only the write registers will change 4 If the write value exceeds the register limit see Register Table then that register value changes to its high or low limit FC17 Rep...

Page 22: ...o word N A N A N A Read Only 40003 Input B Relative Value Hi word N A N A N A Read Only 40004 40005 40006 40007 40009 40011 40013 40017 40015 40019 40008 40010 40012 40014 40018 40016 40020 Calculatio...

Page 23: ...ess specifier the next character is the command character 3 The next character is the Register ID This identifies the register that the command affects The P command does not require a Register ID cha...

Page 24: ...ot change the corresponding output mode U abcde e Analog Output d SP4 c SP3 b SP2 a SP1 Example VU00011 places SP4 and Analog in manual Analog Output Register AOR ID W This register stores the present...

Page 25: ...RMAT Data is transferred from the meter through a serial communication channel In serial communications the voltage is switched between a high and low level at a predetermined rate baud rate using ASC...

Page 26: ...E ANALOG UPDATE TIME to to to Enter the source for the analog output to retransmit Relative net Input Value The Relative Input Value is the Absolute Input Value that includes the Display Offset Value...

Page 27: ...ve selections to be calibrated At each prompt use the PAX arrow keys to adjust the external meter display to match the selection being calibrated When the external reading matches or if this range is...

Page 28: ...K Power level power connections Module 3 programming NO DISPLAY REMEDIES PROBLEM For further assistance contact technical support at the appropriate company numbers listed PARAMETER VALUE CHART Progra...

Page 29: ...RE ASSIGNMENT CALCULATION CONSTANT VALUE CALCULATION FUNCTION MIN CAPTURE DELAY TIME INPUT B OFFSET VALUE MAX CAPTURE DELAY TIME INPUT A OFFSET VALUE CALCULATION FILTER BAND DISPLAY INTENSITY LEVEL US...

Page 30: ...SP t LO t LO AS HI AS HI t SCFAC ASIN dECPt dECPt tbASE Locut P uP PAr INP A CALC INP b tYPE dAtA bAUd SPNt HILO tot Addr dELAY YES Abru OPt NO RLC MODE ONLY ASn n Scaling Style FUNCTION KEYS USER INP...

Page 31: ...31 This page intentionally left blank...

Page 32: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Reviews: