red lion PAXDP User Manual Download Page 22

22

PAXDP FREQUENTLY USED MODBUS REGISTERS

Only frequently used registers are shown below. The entire Modbus Register Table can be found at www.redlion.net. The below limits are shown as Integers or 

HEX < > values. Read and write functions can be performed in either Integers or Hex as long as the conversion was done correctly. Negative numbers are represented 

by two’s complement.

Note: The PAXDP should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors.

1

  For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.

2

  An attempt to exceed a limit will set the register to its high or low limit value.

Bit State: 1= Reset Output; Bit is returned to zero 

following reset processing  

Bit 3 = SP1, Bit 2 = SP2, Bit 1 = SP3, Bit 0 = SP4

Status of Setpoint Outputs: Bit State: 0=Off, 1=On,  

Bit 3 = SP1, Bit 2 = SP2, Bit 1 = SP3, Bit 0 = SP4  

Outputs can only be activated/reset with this register 

when respective bits in Manual Mode (MMR) register 

are set
Bit State: 0=Auto Mode, 1=Manual Mode  

Bit 4 = SP1, Bit 3 = SP2, Bit 2 = SP3, Bit 1 = SP4,  

Bit 0 = Linear Output

Functional only if Linear Output is in manual mode 

(MMR bit 0 = 1). Linear Output Card is written to only  

if Linear Out (MMR bit 0) is set
Gross value of present Input A level. This value is 

affected by Input Type, Resolution, Scaling, but not 

affected by Offset Value
Gross value of present Input B level. This value is 

affected by Input Type, Resolution, Scaling, but not 

affected by Offset Value

Relative Input Value (standard meter value) is sum of 

Input Offset Value and Input Absolute Value 

Setpoint List B

Setpoint List A

Setpoint List A

Setpoint List A

Setpoint List A

Relative Input Value (standard meter value) is sum of 

Input Offset Value and Input Absolute Value 

Input B Relative Value (Lo word)

REGISTER  

ADDRESS 

1

REGISTER NAME

LOW LIMIT 

2

HIGH LIMIT 

2

FACTORY 

SETTING 

ACCESS

COMMENTS

FREQUENTLY  USED  REGISTERS

40001

40002

Input A Relative Value (Hi word)

Input A Relative Value (Lo word)

N/A

N/A

N/A

Read Only

40003

Input B Relative Value (Hi word)

N/A

N/A

N/A

Read Only

40004
40005
40006
40007

40009

40011

40013

40017

40015

40019

40008

40010

40012

40014

40018

40016

40020

Calculation Value (Hi word)
Calculation Value (Lo word)
Maximum Value (Hi word)

Minimum Value (Hi word)

Total Value (Hi word)

Setpoint 1 Value (Hi word)

Setpoint 3 Value (Hi word)

Setpoint 2 Value (Hi word)

Setpoint 4 Value (Hi word)

Maximum Value (Lo word)

Minimum Value (Lo word)

Total Value (Lo word)

Setpoint 1 Value (Lo word)

Setpoint 3 Value (Lo word)

Setpoint 2 Value (Lo word)

Setpoint 4 Value (Lo word)

N/A

-19999

-19999

-199999000

-19999

-19999

-19999

-19999

N/A

99999

99999

999999000

99999

99999

99999

99999

N/A

N/A

N/A

N/A

100

300

200

400

Read Only

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

40021

40022

40023

40024

40025

40027

40026

40028
40029

40041

40039

40035

40037

40033

40031

40030

40042

40040

40036

40038

40034

40032

Setpoint Output Register (SOR)

Manual Mode Register (MMR)

Reset Output Register

Analog Output Register (AOR)

Input A Absolute Value (Hi word)

Input B Absolute Value (Hi word)

Input A Absolute Value (Lo word)

Input B Absolute Value (Lo word)
Input A Offset Value (Hi word)

Alternate Setpoint 1 Value (Hi word)

Main Setpoint 4 Value (Hi word)

Main Setpoint 2 Value (Hi word)

Main Setpoint 3 Value (Hi word)

Main Setpoint 1 Value (Hi word)

Input B Offset Value (Hi word)

Input A Offset Value (Lo word)

Alternate Setpoint 1 Value (Lo word)

Main Setpoint 4 Value (Lo word)

Main Setpoint 2 Value (Lo word)

Main Setpoint 3 Value (Lo word)

Main Setpoint 1 Value (Lo word)

Input B Offset Value (Lo word)

0

0

0

0

N/A

N/A

-19999

-19999

-19999

-19999

-19999

-19999

-19999

15

31

15

4095

N/A

N/A

99999

99999

99999

99999

99999

99999

99999

N/A

0

0

0

N/A

N/A

0

100

400

200

300

100

0

Read/Write 

See Note

Read/Write

Read/Write

Read/Write

Read Only

Read Only

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Read/Write

Calculation Result of Math Function

Process value of present input level. This value is 

affected  by Input Type, Resolution, Scaling &  Offset Value  

(Relative Value = Absolute Input Value + Offset Value)
Process value of present input level. This value is 

affected  by Input Type, Resolution, Scaling &  Offset Value  

(Relative Value = Absolute Input Value + Offset Value)

Summary of Contents for PAXDP

Page 1: ...eadout of totalized flow calculate service intervals of motors or pumps etc The totalizer can also accumulate batch operations The meter has four setpoint outputs implemented on Plug in option cards T...

Page 2: ...S30 Quad Setpoint Sourcing Open Collector Output Card PAXCDS40 PAXCDC RS485 Serial Communications Card with Terminal Block PAXCDC10 Extended RS485 Serial Communications Card with Dual RJ11 Connector P...

Page 3: ...Response Time 20 msec max Logic State Jumper selectable for sink source logic 12 TOTALIZER Function Time Base second minute hour or day Batch Can accumulate gate input display from a user input Time...

Page 4: ...lude PAXCDS10 Dual Relay FORM C Normally open closed PAXCDS20 Quad Relay FORM A Normally open only PAXCDS30 Isolated quad sinking NPN open collector PAXCDS40 Isolated quad sourcing PNP open collector...

Page 5: ...rature and provides good air circulation Placing the unit near devices that generate excessive heat should be avoided The bezel should be cleaned only with a soft cloth and neutral soap product Do NOT...

Page 6: ...to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppres...

Page 7: ...In order to preserve the safety of the meter application the sensor input common must be suitably isolated from hazardous live earth referenced voltages or input common must be at protective earth gro...

Page 8: ...device between appropriate User Input terminal and User Comm DSP 8 8 8 8 8 A C B PAR F1 F2 RST A 1 S P S P S 2 3 P P4 S Display Readout Legends Optional Custom Units Overlay Setpoint Alarm Annunciato...

Page 9: ...listed on the Parameter Value Chart following the programming section ALTERNATING SELECTION DISPLAY In the module description sections which follow the dual display with arrows appears for each progra...

Page 10: ...less than the band value the filter engages again This allows for a stable readout but permits the display to settle rapidly after a large process change The value of the band is in display units ind...

Page 11: ...mA 0 with 20 mA the desired high Display Value The calculations stop at the limits of the Input Range Jumper position 6 For input levels beyond the last programmed Input Value the meter extends the D...

Page 12: ...B Display will normally show the Relative unless switched by this function The Absolute is a gross value based on Module 1 DSP and INP entries without the Display Offset Value The Absolute display is...

Page 13: ...ECTIONS Select main or alternate setpoints Reset Setpoint 1 Alarm 1 Reset Setpoint 2 Alarm 2 Reset Setpoint 3 Alarm 3 Reset Setpoint 4 Alarm 4 Reset Setpoint 3 4 Alarm 3 4 Reset Setpoint 2 3 4 Alarm 2...

Page 14: ...s to be viewed and modified This Programming Mode can be locked with a security code and or user input When locked and the PAR key is pressed the meter enters a Quick Programming Mode In this mode the...

Page 15: ...present MAX value for the entered delay time the meter will capture that display value as the new MAX reading A delay time helps to avoid false captures of sudden short spikes to sec MAX CAPTURE ASSIG...

Page 16: ...ut permits the display to settle rapidly after a large process change The value of the band is in display units independent of the Display Decimal Point position A band setting of 0 keeps the digital...

Page 17: ...Totalizer Decimal Point parameter TOTALIZER HIGH ORDER DISPLAY When the total exceeds 5 digits the front panel annunciator flashes if assigned to A B or C display In this case the meter continues to t...

Page 18: ...with unbalanced hysteresis Deviation high with unbalanced hysteresis Deviation low with unbalanced hysteresis Inside band with unbalanced hysteresis Outside band with unbalanced hysteresis Lower Total...

Page 19: ...0 0 allows the meter to update the alarm status per the response time listed in the Specifications When the output logic is this becomes on time delay Any time accumulated at power off resets during p...

Page 20: ...not be used The PAXCDC1 RS485 or PAXCDC2 RS232 card should be used instead COMMUNICATIONS TYPE RLC Protocol ASCII Modbus RTU Modbus ASCII The Communication Type factory settings must be changed from...

Page 21: ...udes read only registers then only the write registers will change 4 If the write value exceeds the register limit see Register Table then that register value changes to its high or low limit FC17 Rep...

Page 22: ...o word N A N A N A Read Only 40003 Input B Relative Value Hi word N A N A N A Read Only 40004 40005 40006 40007 40009 40011 40013 40017 40015 40019 40008 40010 40012 40014 40018 40016 40020 Calculatio...

Page 23: ...ess specifier the next character is the command character 3 The next character is the Register ID This identifies the register that the command affects The P command does not require a Register ID cha...

Page 24: ...ot change the corresponding output mode U abcde e Analog Output d SP4 c SP3 b SP2 a SP1 Example VU00011 places SP4 and Analog in manual Analog Output Register AOR ID W This register stores the present...

Page 25: ...RMAT Data is transferred from the meter through a serial communication channel In serial communications the voltage is switched between a high and low level at a predetermined rate baud rate using ASC...

Page 26: ...E ANALOG UPDATE TIME to to to Enter the source for the analog output to retransmit Relative net Input Value The Relative Input Value is the Absolute Input Value that includes the Display Offset Value...

Page 27: ...ve selections to be calibrated At each prompt use the PAX arrow keys to adjust the external meter display to match the selection being calibrated When the external reading matches or if this range is...

Page 28: ...K Power level power connections Module 3 programming NO DISPLAY REMEDIES PROBLEM For further assistance contact technical support at the appropriate company numbers listed PARAMETER VALUE CHART Progra...

Page 29: ...RE ASSIGNMENT CALCULATION CONSTANT VALUE CALCULATION FUNCTION MIN CAPTURE DELAY TIME INPUT B OFFSET VALUE MAX CAPTURE DELAY TIME INPUT A OFFSET VALUE CALCULATION FILTER BAND DISPLAY INTENSITY LEVEL US...

Page 30: ...SP t LO t LO AS HI AS HI t SCFAC ASIN dECPt dECPt tbASE Locut P uP PAr INP A CALC INP b tYPE dAtA bAUd SPNt HILO tot Addr dELAY YES Abru OPt NO RLC MODE ONLY ASn n Scaling Style FUNCTION KEYS USER INP...

Page 31: ...31 This page intentionally left blank...

Page 32: ...Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any p...

Reviews: