background image

REC Peak Energy 72 Installation Manual - UL 1703
Rev C.3 - 02.16 

Ref: NE-06-06-C

7

In areas of snow build-up, panels can be subjected to forces in excess of the stated limit even when snow depth does not 

appear extreme, causing damage to the framework.  If the installation is likely to be affected, further suitable panel support is 

recommended, especially on the lower row of panels.

Part Name

Material

Rail

6105 - t5 aluminum extrusion

Bolt

M8 x 25 drop in t-stud kit

Nut

M8 flanged hex nut

When using mounting holes, fixings must be fastened to 16 ft-lbs (21.7 Nm) of torque and installation must be according to fig. 8.

iv)  Installation using mounting holes

ReC Peak energy 72 panels have been evaluated by uL for mounting using the four elongated holes (18/32 in x 11/32 in (14 x 9 mm)) on 

the underside of the panel frame at a distance of 10 

7/16

 in (270 mm) from the short side edge (fig. 7), utilizing rails and bolts matching the  

specifications below.  
Installation of ReC Peak energy 72 panels using mounting holes complies with uL 1703 requirements for a maximum design load of 75.2 

lbs/ft² (3600 Pa).  when installing in this way, the frame and panel edge must be supported by two transverse rails (fig. 1) of aluminium or 

galvanized steel (to avoid galvanic corrosion) suitable for the application and appropriate for the local environment.  these must be held in 

position by bolts and flange nuts according to the specifications below:
observe the following procedures when using mounting holes:

• 

Additional electrical bonding to earth is required for the support structure (see section on grounding).

• 

All four mounting holes in the frame must be used.

• 

fixings must be tightened to 16 ft-lbs (21.7 Nm) using a torque wrench.

The warranty will be voided if additional holes are made in the frame.  All fixing and fastening materials should be corrosion 

resistant.

fig. 7:  Mounting using  

mounting holes

GR

GR

GR

GR

47

47

1/2

 

56 

1/4 

± 

1/16

 

77 

1/2

 

±

 

1/8

 

10 

7/16 

± 

1/16

37 

13/32 

±

 

1/8

39 

±

 0.

1

3/4 

± 

3/16

5/8 

± 

3/16

18/32

11/32

7/

8

3/

4

fig. 6:  Mounting holes

9

.8

 - 13.8”

1”

iii)  long side mounting using clamps

Mounting utilizing clamps on the two long sides of the panel have been found to be in compliance with uL 1703 requirements for a maximum 

design load of 75.2 lbs/ft² (3600 Pa) (fig. 4).

• 

Clamps must be secured between a distance of 9.8 in to 13.8 in (250 mm - 350 mm) from the clamp centerline to the end of the panel.

• 

tightening torque must be tightened to 16 ft-lbs (21.7 Nm).

• 

the distance between the end clamp and the end of the rail must be minimum 1 in (25 mm).

fig. 4:  Long side mounting

fig. 5: 

An array mounting system with each panel secured at four points.

Summary of Contents for Peak Energy 72

Page 1: ...Installation manual rec Peak energy 72 FortheinstallationofallRECPeakEnergy72 solarpanels certifiedaccordingtoUL1703...

Page 2: ...Safetyintheworking area 4 ii Preventing currentgeneration 4 iii Specific hazards of DC electricity 4 iv Safetyrequirements 4 MECHANICAL INSTALLATION 5 FIRE GUIDELINES 5 ORIENTATION 5 ENVIRONMENTAL FA...

Page 3: ...ty or personal safety Indicates important notes on best practice to help with the installation or to avoid potential damage to the panels array or property For further information on installation proc...

Page 4: ...st be followed to address these increased outputs In installations not under the requirements of the NEC the values of ISC andVOC marked on the panels must be multiplied by a factor of 1 25 when deter...

Page 5: ...ocal authorities for applicable regulations concerning setbacks or other restrictions that may apply for ground mounted solar arrays The use of DC ground fault interrupters is recommended Check whethe...

Page 6: ...kling load min 7 8 in 2 0 mm Moment of Inertia for profile area about X X min array mounting diagram 13 34 in4 192 mm4 Fig 1 Panel mounting options The overlap between support rail and the outer edge...

Page 7: ...ails fig 1 of aluminium or galvanized steel to avoid galvanic corrosion suitable for the application and appropriate for the local environment These must be held in position by bolts and flange nuts a...

Page 8: ...ut 10 ensuring a conductive connection fig 9 Tighten according to manufacturer s instructions Fig 9 Recommended grounding Cross section AWG Type Torque in lbs 4 6 Stranded 35 8 Stranded 25 10 14 Stran...

Page 9: ...ing points to ground are tight secure and free from corrosion which could break the continuity between the panels and ground Recycling REC has made every effort to ensure panel packaging is kept to a...

Page 10: ...rated 4 mm solar cable 47 47 4 mm connectors MC4 connectable ELECTRICAL DATA STC REC285PE REC290PE REC295PE rec300pe REC305PE REC310PE REC315PE REC320PE REC325PE NominalPower PMPP Wp 285 290 295 300...

Page 11: ...ction 48 12 2014 B 3 Revision of low light behavior in Electrical Data 02 2014 B 4 Updates to cable length 47 Type 2 System Fire Class rating addition of Connections chapter 03 2015 C Updates required...

Page 12: ...RECSolarPte Ltd 20TuasSouthAvenue14 Singapore637312 Singapore Tel 6564959228 Mail post recgroup com www recgroup com...

Reviews: