UMHPI
Industrial inverter air/water heat pumps with axial fans
10
DO1E
H63
DO1E (phase)
DO1EN (neutral)
22
Plant auxiliary heater
See paragraph 8.1.1
Under voltage output single-phase 230Vac,
50Hz, 5A resistives, 1A inductives.
DO2E
H64
DO2E (phase)
DO2EN (neutral)
26
DHW auxiliary heater
See paragraph 8.1.3
Under voltage output single phase 230Vac,
50Hz, 5A resistives, 1A inductives.
DO3E
H65
DO3E (phase)
DO3EN (neutral)
29
Boiler activation
See paragraph 8.2
Under voltage output single phase 230Vac,
50Hz, 5A resistives, 1A inductives.
(3)
DO4E
H66
DO4E (fase)
DO4EN (neutro)
0 Not
set
Under voltage output single phase 230Vac,
50Hz, 5A resistives, 1A inductives.
(3)
DO5E
H67
DO5E (fase)
DO5EN (neutro)
0 Not
set
Under voltage output single phase 230Vac,
50Hz, 5A resistives, 1A inductives.
OC1
H68
NO1E (phase)
N1E (neutral)
NC1E (phase)
25
Double setpoint command
valve
See paragraph 8.4
Switching contact, single phase voltage
230Vac, 50Hz, 5A resistive, 1A inductive.
-
NO1= Normally open
-
NC1= Normally-Closed
(3)
OC2
H69
NO2E (phase)
N2E (neutral)
NC2E (phase)
0 Not
set
Switching contact, single phase voltage
230Vac, 50Hz, 5A resistive, 1A inductive.
-
NO2= Normally open
-
NC2= Normally-Closed
(3)
Not selectable in the models of UMHPI V.
7
OPERATION LOGIC
The following operation logics are enabled by the master controller (CB), mounted on the front panel of the unit.
7.1
DYNAMIC SETPOINT ADJUSTMENT
The controller can change the setpoint by adding a value depending on the outdoor air temperature sensor. In this case, you need
to change the values of the parameters from
b08
to
b14
following the indications below (settings to be done by the installer):
Parameters of the controller
PAr->rE->
•
b08
=
dynamic setpoint, enabled
= 1/
disabled
=
0 (this parameter must be disabled in the case of the use of climatic
compensation by the optional remote touch screen panel Evo Touch).
•
b09
=
offset max in cooling mode operation.
•
b10
=
offset max in heating mode operation.
•
b11
=
Outdoor temperature setting in cooling mode.
•
b12
=
Outdoor temperature setting in heating mode.
•
b13
=
Temperature difference in cooling mode operation.
•
b14
=
Temperature difference in heating mode operation.
Please see paragraph 11.4 for to change the parameters.
Curve of the setpoint variation as a function of the outside temperature:
Cooling