UMHPI
Industrial inverter air/water heat pumps with axial fans
26
8.3.3
IN JOINT OPERATION (AREA II)
If the outdoor air temperature is included between
r28
and
r08
, the compressor will operate in synergy with the auxiliary electric
heaters.
In this operation area, the devices will start operation in the following working order: at first the boiler will start the operation,
then the heat pump and the plant circuit auxiliary electric heaters will start operation after a period of time given by
r12
(in
minutes)
and after
r16
(in minutes) the DHW auxiliary electric heaters will start operation.
The activation priorities are defined by the following parameters
r14
,
r20
,
r23
and
r24
.
The operation becomes
normal
if the temperature increases above the value of
r28
+1,0°C.
Note:
In the joint operation, the temperature of the boiler is adjusted by the water temperature remote sensor of the plant circuit
(if enabled), particularly if the temperature measured by this remote sensor is less than the setpoint
Hea
, the boiler will be
activated, and then will be deactivated when the measured temperature by the remote sensor is greater than setpoint
Hea
.
The boiler will be managed by the outlet temp. sensor of the heat pump if the water plant circuit remote sensor is not active.
8.3.4
IN SUBSTITUTION OPERATION
If the outdoor air temperature decreases below
r08
,
the compressor operation will be inhibited.
If the auxiliary system is composed of the plant circuit and/or the DHW electric heaters, they will be activated in substitution
to the compressor with a duration defined by
r12
(minutes) for the plant circuit side and by
r16
(minutes) for the domestic
hot water side.
During the substitution operation, instead it is not necessary to enable the auxiliary electric heaters with the parameter
r10
or
r15
, because the auxiliary electric heaters operate in substitution (and not as auxiliary heating systems) to the heat pump
(therefore it is enough to select the type of utilization of the auxiliary electric heaters by setting only the parameter
r24
).
If the auxiliary system is a boiler with its proper circulator (
r32
=
1
or
3
).
The circulator of the heat pump will be off, the boiler will be enabled after
P01
(default 30 seconds).
Note:
When the defrosting protection occurs on the water side, the utilization pump will be activated (or remains on).
If the in substitution auxiliary system is a boiler with its proper temperature control (
r32
=
2
or
3
).
The boiler will be enabled independently than thermoregulation of the heat pump.
If the in substitution auxiliary system is a boiler without circulator (
r32
=
0
or
2
).
The circulator of the heat pump will be active when the boiler is enabled.
The compressor will be enabled again if the temperature increases above the value of
r08
+
r09
(°C) (by default r09=1,0°C)
8.3.5
OPERATION AREA - ACTIVATION OF THE AUXILIARY ELECTRIC HEATER AND BOILER (Plant circuit water
temperature sensor is not enabled)
The possible configurations of the parameters related to auxiliary heaters are listed below in the tables 1, 2, 3 and 4, that are
divided by areas of operation (the columns of "MODE" and "
rxx
" parameters indicate the operation mode and the possible values
of the parameters for allowing the auxiliary heaters to intervene according to a predefined order of intervention, when the unit is
running in a certain type of operation; several modes and values of the parameters can be alternatively selected and they are
reported in the same cell separated by the symbol "/").
TABLE 1. NORMAL OPERATION IN HEAT PUMP MODE
N°
ORDER OF INTERVENTION OF
AUXILIARY ELECTRIC HEATERS
(when
the setpoint is not achieved and the
unit is in alarm condition)
MODE
OPERATION
r10
r15
r12
r16
r23
r24
1
1) Auxiliary electric heater of plant
HEAT/HEAT+SAN
HEAT
1
0/1/2
/
/ 0/2/5
1/3
2
1)
Boiler
HEAT/HEAT+SAN
HEAT 0/1
0/1/2
/ /
1/3/4/6
0/2
3
1) Auxiliary electric heater of plant
2) After r12 minutes,
Boiler
HEAT/HEAT+SAN HEAT 1
0/1/2
Set up of
minutes
/ 1/3 1/3
4
1)
Boiler
2) After r12 minutes
, plant auxiliary
electric heater
HEAT/HEAT+SAN
HEAT 1
0/1/2
Set up of
minutes
/ 4/6 1/3
5
1) Auxiliary electric heater of DHW
HEAT+SAN
SAN
0/1
1
/ /
0/1/4
2/3
6 1)
Boiler
HEAT+ SAN /
COOL+ SAN
SAN 0/1
0/1/2
/ /
2/3/5/6
0/1
7
1) Auxiliary electric heater of DHW
2) After r15 minutes,
boiler
HEAT+ SAN
SAN
0/1
1
/
Set up of
minutes
2/3 2/3
8
1)
Boiler
2) After r15 minutes,
auxiliary electric
heater of DHW
HEAT+SAN SAN
0/1
1
/
Set up of
minutes
5/6 2/3
9
1) Auxiliary electric heater of
Plant/DHW
HEAT/HEAT+SAN In HEAT OR in SAN
1
1
/
/
0
3
10 1)
Boiler
HEAT/HEAT+SAN In HEAT OR in SAN 0/1
0/1/2
/
/
3/6
0
11
1) Auxiliary electric heater of plant/DHW
2) After r12 minutes,
Boiler
HEAT /
HEAT+ SAN
In HEAT OR in SAN
1
1
Set up of
minutes
Set up of
minutes
3 3
12
1)
Boiler
2) After r12 minutes,
auxiliary electric
heater of plant/DHW
HEAT /
HEAT+ SAN
In HEAT OR in SAN
1
1
Set up of
minutes
Set up of
minutes
6 3