41
6.4
PERFORMANCE ACCORDING TO COMMISSION REGULATION (EU) NO 1253/2014
PRESTAZIONI SECONDO REGOLAMENTO (UE) NO 1253/2014
European Union Commission Regulation (EU) No 1253/2014
Ecodesign Requirements for Ventilation Units
Annex IV
Information requirements [fiche] for RVUs as referred to in Article 4(1)
a)
Manufacturer: Polypipe Ventilation
b)
Model:
Silavent HRX
c)
Specific Energy Consumption (SEC) kWh/(m²a) and Class:
Control typology and CTRL factor n)
Manual
Clock
Central demand
Local demand
1
0.95
0.85
0.65
Cold
-77
A+
-79
A+
-82
A+
-86
A+
Average
-35
A
-37
A
-39
A
-43
A+
Warm
-11
E
-12
E
-14
E
-17
E
d)
Article 2 typology:
i)
Residential Ventilation Unit (RVU)
ii)
Bidirectional (BVU)
e)
Drive Variable speed drive
f)
Recuperative heat exchanger
g)
Thermal efficiency of heat recovery 84% at reference flow rate
h)
Maximum flow rate 253 m³/h at 100Pa. This unit is for residential use only.
i)
Power input at maximum flow rate 105 W
j)
Sound power level (LWA) 61 dB
k)
Reference flow rate 0.053 m³/s
l)
Reference pressure difference 50 Pa
m)
Reference Specific Power Input (SPI) 0.27 W/(m³/h)
n)
see c)
o)
Leakage rates at reference flow rate
i)
Maximum internal <5%
ii)
Maximum external <5%
p)
not applicable
q)
not applicable until January 2018
r)
not applicable
s)
Recycling disassembly instruction - go to www.polypipe.com/toolbox
t)
not applicable
u)
not applicable