32
7.1.7
Expert Settings Battery
In some instances individual target values may need to be changed in the battery configuration.
Below is the procedure:
Caution: Please do not change the pre-configured values without prior consultation with RCT Power!
Step
Description
1
Launch “RCT Power APP“ and establish connection to the inverter
(see 7.1.2)
2
Follow the following menu path:
DEVICE → Settings → Battery
Available settings options:
•
SOC target selection
-
Internal [recommended]:
The system determines the Battery SOC target value
taking into account the parameters and
specifications of the solar system installation.
-
Constant:
The battery system attempts to charge the battery to the
value set in option "Force SOC target".
External:
An external device provides the SOC target value, e.g. an
in-house controller, a weather forecast device etc.
•
Min SOC target
Minimum SOC value that can be achieved
(0,00
≙
0%). Default setting: 0.07.
•
Min SOC target (island)
Minimum SOC value that can be achieved in island mode
(0,00
≙
0%). Default setting: 0.07.
•
Max SOC target
Maximum SOC value that can be achieved
(1,00
≙
100%). Default setting: 0.97
•
Force SOC target
SOC tar
get value in setting “Constant“