ST-72 User's Manual
Document: UM-1007
Revision Level A
87
Override 8
Alarm
N/A
40168 40168 N/A
3
6, 16
Alarm for this override
channel to use.
Alarm 1
= 0,
Alarm 2 = 1,
Alarm 3 = 2
5.3.7
STANDARD RELAY 3
Type
Channel First
Last
Block
Size
Read
FC
Write
FC
Notes
A1 Votes
N/A
40180 40180 N/A
3
6, 16
Alarm 1 channels
required. 0 - 64
A2 Votes
N/A
40181 40181 N/A
3
6, 16
Alarm 2 channels
required. 0 – 64
A3 Votes
N/A
40182 40182 N/A
3
6, 16
Alarm 3 channels
required. 0 - 64
Acknowledge N/A
40183 40183 N/A
3
6, 16
Relay is
acknowledgeable.
No
=
0, Yes = 1
Failsafe
N/A
40184 40184 N/A
3
6, 16
Relay is failsafe.
No
= 0,
Yes = 1
Zone 1
Enable
N/A
40185 40185 N/A
3
6, 16
Use zone 1 channels for
voting. No = 0,
Yes
= 1
Zone 2
Enable
N/A
40186 40186 N/A
3
6, 16
Use zone 2 channels for
voting. No = 0,
Yes
= 1
Zone 3
Enable
N/A
40187 40187 N/A
3
6, 16
Use zone 3 channels for
voting. No = 0,
Yes
= 1
Zone 4
Enable
N/A
40188 40188 N/A
3
6, 16
Use zone 4 channels for
voting. No = 0,
Yes
= 1
Zone 5
Enable
N/A
40189 40189 N/A
3
6, 16
Use zone 5 channels for
voting. No = 0,
Yes
= 1
Zone 6
Enable
N/A
40190 40190 N/A
3
6, 16
Use zone 6 channels for
voting. No = 0,
Yes
= 1
Zone 7
Enable
N/A
40191 40191 N/A
3
6, 16
Use zone 7 channels for
voting. No = 0,
Yes
= 1
Zone 8
Enable
N/A
40192 40192 N/A
3
6, 16
Use zone 8 channels for
voting. No = 0,
Yes
= 1
Summary of Contents for ST-72
Page 106: ...ST 72 User s Manual Document UM 1007 Revision Level A 100...
Page 108: ...ST 72 User s Manual Document UM 1007 Revision Level A 102 Figure 6 4...
Page 128: ...ST 72 User s Manual Document UM 1007 Revision Level A 122 8 5 3 COPY CHANNELS Figure 8 7...
Page 129: ...ST 72 User s Manual Document UM 1007 Revision Level A 123 8 5 4 PROGRAMMABLE RELAYS Figure 8 8...