ST-72 User's Manual
Document: UM-1007
Revision Level A
75
Warmup
N/A
12025 12025 N/A
2
N/A
Not in warmup = 0
In warmup = 1
Standard
Relay 1
Flashing
N/A
12026 12020 N/A
4
N/A
False = 0, True = 1.
Indicates whether
standard relay 1 has been
acknowledged.
Standard
Relay 2
Flashing
N/A
12027 12027 N/A
4
N/A
False = 0, True = 1.
Indicates whether
standard relay 2 has been
acknowledged.
Standard
Relay 3
Flashing
N/A
12028 12028 N/A
4
N/A
False = 0, True = 1.
Indicates whether
standard relay 3 has been
acknowledged.
Fault Relay
Flashing
N/A
12029 12029 N/A
4
N/A
False = 0, True = 1.
Indicates whether the
fault has been
acknowledged.
Horn Relay
Flashing
N/A
12034 12034 N/A
4
N/A
False = 0, True = 1.
Indicates whether the
horn relay has been
acknowledged.
Channel Data
Alarm 1
Status
1-64
13449 13512 1
2
N/A
Off = 0, On = 1
Alarm 1
Flashing
1-64
13513 13576 1
2
N/A
Off = 0, On = 1
Alarm 2
Status
1-64
13577 13640 1
2
N/A
Off = 0, On = 1
Alarm 2
Flashing
1-64
13641 13704 1
2
N/A
Off = 0, On = 1
Alarm 3
Status
1-64
13705 13768 1
2
N/A
Off = 0, On = 1
Alarm 3
Flashing
1-64
13769 13832 1
2
N/A
Off = 0, On = 1
Fault Status 1-64
13833 13896 1
2
N/A
Off = 0, On = 1
Summary of Contents for ST-72
Page 106: ...ST 72 User s Manual Document UM 1007 Revision Level A 100...
Page 108: ...ST 72 User s Manual Document UM 1007 Revision Level A 102 Figure 6 4...
Page 128: ...ST 72 User s Manual Document UM 1007 Revision Level A 122 8 5 3 COPY CHANNELS Figure 8 7...
Page 129: ...ST 72 User s Manual Document UM 1007 Revision Level A 123 8 5 4 PROGRAMMABLE RELAYS Figure 8 8...