ST-72 User's Manual
Document: UM-1007
Revision Level A
80
5.3.4
HOLDING REGISTERS
Type
Channel First
Last
Block
Size
Read
FC
Write
FC
Notes
Alarm
Reset
N/A
40001 40001 N/A
3
6, 16
Simulates the alarm reset
button. Write a value of 1
to activate.
System
Name
N/A
40010 40017 N/A
3
6, 16
Character string, 2
characters per register
Date, Year N/A
40020 40020 N/A
3
6, 16
0000 - 9999
Date, Mon N/A
40021 40021 N/A
3
6, 16
0 – 12
Date, Day
N/A
40022 40022 N/A
3
6, 16
0 – 31
Time,
Hour
N/A
40023 40023 N/A
3
6, 16
0 – 23
Time, Min
N/A
40024 40024 N/A
3
6, 16
0 – 59
Time, Sec
N/A
40025 40025 N/A
3
6, 16
0 – 59
Warmup
Time
N/A
40027 40027 N/A
3
6, 16
Time in minutes. 0 – 5
Cal Purge
Time
N/A
40028 40028 N/A
3
6, 16
Time in minutes. 0 – 5
Block
Negative
N/A
40029 40029 N/A
3
6, 16
No
= 0, Yes = 1
Zone Names
Zone 1
Name
N/A
40030 40037 N/A
3
6, 16
Character string, 2
characters per register
Zone 2
Name
N/A
40038 40045 N/A
3
6, 16
Character string, 2
characters per register
Zone 3
Name
N/A
40046 40053 N/A
3
6, 16
Character string, 2
characters per register
Zone 4
Name
N/A
40054 40062 N/A
3
6, 16
Character string, 2
characters per register
Zone 5
Name
N/A
40062 40069 N/A
3
6, 16
Character string, 2
characters per register
Summary of Contents for ST-72
Page 106: ...ST 72 User s Manual Document UM 1007 Revision Level A 100...
Page 108: ...ST 72 User s Manual Document UM 1007 Revision Level A 102 Figure 6 4...
Page 128: ...ST 72 User s Manual Document UM 1007 Revision Level A 122 8 5 3 COPY CHANNELS Figure 8 7...
Page 129: ...ST 72 User s Manual Document UM 1007 Revision Level A 123 8 5 4 PROGRAMMABLE RELAYS Figure 8 8...