ST-72 User's Manual
Document: UM-1007
Revision Level A
84
Override 7
Alarm
N/A
40126 40126 N/A
3
6, 16
Alarm for this override
channel to use.
Alarm 1
= 0,
Alarm 2 = 1,
Alarm 3 = 2
Override 8
Channel
N/A
40127 40127 N/A
3
6, 16
Create an override
channel.
0
is disabled. 0 -
64
Override 8
Alarm
N/A
40128 40128 N/A
3
6, 16
Alarm for this override
channel to use.
Alarm 1
= 0,
Alarm 2 = 1,
Alarm 3 = 2
5.3.6
STANDARD RELAY 2
Type
Channel First
Last
Block
Size
Read
FC
Write
FC
Notes
A1 Votes
N/A
40140 40140 N/A
3
6, 16
Alarm 1 channels
required. 0 - 64
A2 Votes
N/A
40141 40141 N/A
3
6, 16
Alarm 2 channels
required. 0 – 64
A3 Votes
N/A
40142 40142 N/A
3
6, 16
Alarm 3 channels
required. 0 - 64
Acknowledge N/A
40143 40143 N/A
3
6, 16
Relay is acknowledgeable.
No
= 0, Yes = 1
Failsafe
N/A
40144 40144 N/A
3
6, 16
Relay is failsafe.
No
= 0,
Yes = 1
Zone 1
Enable
N/A
40145 40145 N/A
3
6, 16
Use zone 1 channels for
voting. No = 0,
Yes
= 1
Zone 2
Enable
N/A
40146 40146 N/A
3
6, 16
Use zone 2 channels for
voting. No = 0,
Yes
= 1
Zone 3
Enable
N/A
40147 40147 N/A
3
6, 16
Use zone 3 channels for
voting. No = 0,
Yes
= 1
Zone 4
Enable
N/A
40148 40148 N/A
3
6, 16
Use zone 4 channels for
voting. No = 0,
Yes
= 1
Summary of Contents for ST-72
Page 106: ...ST 72 User s Manual Document UM 1007 Revision Level A 100...
Page 108: ...ST 72 User s Manual Document UM 1007 Revision Level A 102 Figure 6 4...
Page 128: ...ST 72 User s Manual Document UM 1007 Revision Level A 122 8 5 3 COPY CHANNELS Figure 8 7...
Page 129: ...ST 72 User s Manual Document UM 1007 Revision Level A 123 8 5 4 PROGRAMMABLE RELAYS Figure 8 8...