background image

SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 5

Table 3 - Equivalent Breeching & Chimney Size

Model

Size

Model

Size

Size

 in (mm)

Size

 in (mm)

  420

10 (254)

1580

18 (457)

  530

10 (254)

1685

18 (457)

 630

12 (305)

1700

20 (508)

  735

14 (356)

1900

20 (508)

  840

14 (356)

2000

22 (559)

  950

14 (356)

2400

24 (610)

1050

16 (406)

2800

26 (660)

1160

16 (406)

3200

28 (711)

1260

16 (406)

3600

30 (762)

1370

18 (457)

4000

30 (762)

1470

18 (457)

Note:  These sizes are based on a 20 foot (6.1m) chimney height.

When more than one appliance is connected to the
same chimney flue the flue must be large enough to
safely vent the combined output of all the appliances.

WARNING: If an appliance using any type of a
mechanical draft system operating under
positive pressure is connected to a chimney
flue, never connect any other appliances to this
flue. Doing so can result in the accumulation of
carbon monoxide which can cause severe
personal injury or death!

VENT CONNECTIONS

Always use a type B or single wall galvanized metal vent
pipe the same diameter as the draft diverter flue collar.
Use the shortest, straightest vent system possible for
the installation. If horizontal runs exceed 6 feet (1.8 m)
they must be supported at 6 foot (1.8 m) intervals with
overhead hangers. The vent system should be sloped
up toward the chimney at a minimum rate of 1/4 inch/
foot (2 cm/m) and terminate flush with the inside of the
chimney flue. Fasten each connection with at least 3
corrosion resistant sheet metal screws.

WARNING: Never modify or alter any part of the
boiler’s draft diverter. This includes the removal
or alteration of any baffles. Never install a vent
pipe of a diameter different than that of the
boiler draft hood flue collar. Failure to comply
with this warning can result in severe personal
injury or death.

Always provide a minimum clearance of 6 inches
(152 mm) between type C vent pipe and any
combustible materials. Type B1 vent may be used,
clearance between it and any combustible material must
be as listed.

WARNING: Failure to maintain minimum
clearances between vent connectors and any
combustible material can result in a fire causing
extensive property damage, severe personal
injury or death!

COMMON VENT SYSTEMS

If an existing boiler/water heater is removed from a
common venting system, the common venting system
may then be too large for the proper venting of the
remaining appliances connected to it. At the time of
removal of an existing boiler/water heater, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining
connected to the common venting system are not in
operation.

Au moment du retrait d’une chaudière existante, les
mesures suivantes doivent être prises pour chaque
appareil toujours raccordé au système d’évacuation
commun et qui fonctionne alors que d’autres appareils
toujours raccordés au système d’évacuation ne fonction-
nent pas: système d’évacuation

a) Seal any unused openings in the common venting

system.

Sceller toutes les ouvertures non utilisées du sys-
tème d’évacuation.

b) Visually inspect the venting system for proper size

and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.

Inspecter de façon visuelle le système d’évacu-ation
pour déterminer la grosser et l’inclinaison
horizontale qui conviennent et s’assurer que le
système est exempt d’obstruction, d’étranglement
de fruite, de corrosion et autres défaillances qui
pourraient présenter des risques.

Summary of Contents for 8800 Series

Page 1: ...roperty damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try...

Page 2: ...le efficient operation and long life for which this heating boiler water heater was designed these instructions must be read understood and followed The Series 8800 and 8900 finned copper heating boil...

Page 3: ...mply with this warning may result in a fire causing extensive property damage severe personal injury or death 4 Locate the boiler water heater in an area that will prevent water damage to adjacent con...

Page 4: ...re communicating with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 in2 2000 Btu hr 1100 mm2 kW of the total input rating of all of the equipment in the enclos...

Page 5: ...ollar Failure to comply with this warning can result in severe personal injury or death Always provide a minimum clearance of 6 inches 152 mm between type C vent pipe and any combustible materials Typ...

Page 6: ...e fa or ad quate Remettre les portes et les fen tres les ventilateurs les registres de chemin es et les appareils au gaz leur position originale g Any improper operation of the common venting system s...

Page 7: ...outside of the range listed in Table 5 indicates that the flow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty The maximum allowable flow rate th...

Page 8: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 8 Figure 1 Typical Primary Secondary Piping System Figure 2 Low Temperature Piping...

Page 9: ...8 3 42 4 59 9 34 3 40 8 47 6 54 4 61 6 68 1 75 2 81 7 88 8 95 2 102 4 109 2 116 0 123 1 131 2 157 4 183 6 209 9 236 1 2 2 2 6 3 0 3 4 3 9 4 3 4 7 5 2 5 6 6 0 6 5 6 9 7 3 7 9 8 3 9 9 11 6 13 2 14 9 0 6...

Page 10: ...ed with bronze headers Piping and components connected to the water heater must be suitable for use with potable water The water heater must not be connected to any heating system piping or components...

Page 11: ...er heater inlet must not be less than 110 F 43 C or excessive condensation of the products of combustion will damage the water heater voiding the warranty The method outlined below can be employed to...

Page 12: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 12 Figure 5 Typical Water Heating Piping Figure 6 Multiple Water Heating Piping...

Page 13: ...0 1100 2100 3300 5900 12 000 40 245 500 760 1450 2300 4100 8300 50 215 440 670 1270 2000 3600 7400 60 195 400 610 1150 1850 3250 6800 80 170 350 530 990 1600 2800 5800 100 150 305 460 870 1400 2500 51...

Page 14: ...rol valve to the appliance Do Not interrupt water flow through the boiler water heater En cas de surchauffe ou si l alimentation en gaz ne s arr te pas fermez manuellement le robinet d arr t de l admi...

Page 15: ...6 Wait five 5 minutes to clear out any gas Then small for gas including near the floor If you smell gas STOP Follow B in the safety infomration above If you don t smell gas go to next step 7 Connect...

Page 16: ...ing probe Figure 8 To adjust the pilot the following steps must be taken 1 Remove the pilot gas pressure regulator cap 2 Turn the pressure regulator adjustment screw clock wise to increase the flame a...

Page 17: ...ticipator setting may be necessary if the unit cycles frequently If the room temperature over shoots the thermostat setting reduce the anticipator setting Water Heater Operation Controls The operating...

Page 18: ...Exchanger Replacement 1 Sagging or distorted heat exchanger tubes are an indication of low water flow through the system 2 A damaged heat exchanger must be replaced and the condition that caused the d...

Page 19: ...rn Header 8 Black O Rings 9 Stud Bolts 10 Flange Nuts 11 V Baffle 12 Frame Assembly 13 Main Burner 14 Union 15 Firing Valve 16 Main Gas Valve 17 A Valve 18 Refractory 19 Flue Collector End 20 Down Dra...

Page 20: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 Lower Left Right Jacket End Pnl 72 0016 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 Inlet Outlet Header Cast Iron 01 0001 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Inlet Outlet Header Bronze 01...

Page 21: ...17 19 21 23 25 27 29 31 33 35 Burner Tube Stainless w Bracket 70 0500 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 14 Union 1 53 0054 1 1 1 1 1 1 Union 1 1 4 53 0055 1 1 1 1 1 1 1 Union 1 1 2 53 0056 1 1 15 Firing...

Page 22: ...70 1 70 0371 1 70 0372 1 70 0373 1 70 0374 1 70 0375 1 70 0376 1 70 0377 1 Upper Front Refractory Channel 70 0177 1 70 0178 1 70 0179 1 70 0180 1 70 0181 1 70 0182 1 70 0183 1 70 0184 1 70 0185 1 70 0...

Page 23: ...1 70 0035 1 70 0036 1 70 0037 1 70 0038 1 70 0039 1 70 0040 1 70 0041 1 70 0042 1 70 0043 1 70 0044 1 22 Upper Front Jacket Panel 72 0001 1 72 0002 1 72 0003 1 72 0004 1 72 0005 1 72 0006 1 72 0007 1...

Page 24: ...07 1 72 0008 1 72 0009 1 72 0010 1 72 0011 1 72 0012 1 72 0013 1 72 0014 1 72 0015 1 29 Burner Drawer Side Rail Assy Left 70 0361 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Burner Drawer Side Rail Assy Right 70 03...

Page 25: ...Operator L4008A US only 14 0102 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Operator GIP 9868 CAN only 14 0116 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Operator L6008A 1242 Water Heaters 14 0106 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1...

Page 26: ...1 0154 1 21 0155 1 21 0156 1 21 0157 1 21 0158 1 21 0159 1 21 0160 1 Not Shown Natural to LP Conversion Kit 21 0161 1 2000 to 4500 feet 21 0162 1 21 0163 1 21 0164 1 21 0165 1 21 0166 1 21 0167 1 21 0...

Page 27: ...rn Header 8 Copper Fin Tube 9 Black O Rings 10 Stud Bolts 11 Flange Nuts 12 V Baffle 13 Frame Assembly 14 Main Burner 15 Union 16 Firing Valve 17 Main Gas Valve 18 A Valve 19 Burner Drawer Side 20 Ref...

Page 28: ...0001 32 32 32 32 32 32 10 Stud Inlet Outlet Return Headers 57 0223 24 24 24 24 24 24 11 Nut Inlet Outlet Return Headers 57 0491 24 24 24 24 24 24 12 Heat Exchanger V Baffle 03 1147 15 03 1148 15 03 11...

Page 29: ...nd Refractory Panel Left Right 05 0050 2 2 2 2 2 2 Not Shown Center Refractory Panel 05 0051 4 4 6 8 8 10 20 Corner Refractory Panel 05 0052 4 05 0053 4 05 0054 4 05 0055 4 05 0056 4 05 0057 4 21 Draf...

Page 30: ...1 1 1 Operator L6008G1009 2 Stage 14 0107 1 1 1 1 1 Operator T991E 1018 Modulating Boilers 14 0108 1 1 1 1 1 Operator T991E 1034 Modulating Water Heaters 14 0110 1 1 1 1 1 Operator T6031A 1052 Pool H...

Page 31: ...re between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace S8610 module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused by high or...

Page 32: ...eup valve is open and functioning Remove return header and inspect the heat exchanger tubes Ensure relief valve is properly sized for the system never exceed 160 psi Ensure expansion tank is properly...

Reviews: