SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 3

RATINGS & CAPACITIES

Before undertaking the installation of the Series 8800
and 8900 boiler/water heater check the rating plate to
ensure that the unit has been sized properly for the job.
The “Net I=B=R Ratings” specify the equivalent amount
of direct cast iron radiation that the unit can supply under
normal conditions. Also ensure that the unit has been
set up for the type of gas available at the installation
site. Other important considerations are the availability
of an adequate electrical supply, fresh air for combustion
and a suitable chimney or vent system.

BOILER/WATER HEATER LOCATION

1.

Locate the boiler/water heater in an area that
provides good access to the unit. Servicing may
require the removal of jacket panels. Allow the
minimum clearances between adjacent construction
and the boiler/water heater as listed in Table 1.
Accessibility clearances must take precedence over
fire protection clearances.

Table 1 - Clearance to Combustibles

8800/8900

Top

24"

610 mm

Back

24"

610 mm

Left Side

24"

610 mm

Right Side

24"

610 mm

Front

48"

1220 mm

Flue

6"

152 mm

2.

An optimum site will be level, central to the piping
system, close to a chimney and have adequate fresh
air for combustion. Ensure that the boiler/water heater
is level from front to back and from side to side. Use
metal shims to level the boiler/water heater. Electrical
and electronic components must also be protected
from exposure to water during operation and
maintenance. 

DO NOT

 install this boiler/water heater

in a location that would subject any of the gas ignition
components to direct contact with water or excessive
moisture during operation or servicing.

3.

Ensure that the floor is structurally sound and will
support the weight of the boiler/water heater. Never
install a Series 8800 or 8900 boiler/water heater on
a concrete floor that contains wires, cables, water
pipes or hoses. This boiler/water heater is designed
for noncombustible floors only! Never install this
boiler/water heater on combustible materials or
carpeting even if a non-combustible foundation
material is placed over them!

WARNING: Never install a Series 8800 or 8900
boiler/water heater on top of combustible
flooring! Failure to comply with this warning may
result in a fire causing extensive property
damage, severe personal injury or death!

4.

Locate the boiler/water heater in an area that will
prevent water damage to adjacent construction
should a leak occur or during routine maintenance.
If such a location doesn’t exist, a suitable drain pan
that’s adequately drained must be installed under
the unit. The pan must not restrict the flow of
combustion air to the unit.

5.

DO NOT

 place this boiler/water heater in a location

that would restrict the introduction of combustion air
into the unit or subject it to a negative pressure.

6.

NEVER

 place this boiler/water heater in a location

that would subject it to temperatures at or near
freezing.

WARNING: Never store combustible materials,
gasoline or any product containing flammable vapors
or liquids in the vicinity of the boiler/water heater.
Failure to comply with this warning can result in an
explosion or fire causing extensive property damage,
severe personal injury or death!

COMBUSTION AIR & VENTILATION

WARNING: This boiler/water heater must be
supplied with combustion air in accordance with
Section 5.3, Air for Combustion & Ventilation, of
the latest revision of the National Fuel Gas
Code, ANSI Z223.1 and all applicable local
building codes. Canadian installations must
comply with CAN/ CGA B149.1 or .2 Installation
Code for Gas Burning Appliances and
Equipment, or applicable provisions of the local
building codes. Failure to provide adequate
combustion air for this boiler/water heater can
result in excessive levels of carbon monoxide
which can result in severe personal injury or
death!

To operate properly and safely this boiler/water heater
requires a continuous supply of air for combustion.

NEVER

 store objects on or around the boiler!

CAUTION: Combustion air contaminated with
fluorocarbons or other halogenated compounds
such as cleaning solvents and refrigerants will
result in the formation of acids in the combustion
chamber. These acids will cause premature failure
of the boiler/water heater voiding the warranty!

Buildings will require the installation of a fresh air duct
or other means of providing make-up air. Any building
utilizing other gas burning appliances, a fireplace, wood
stove or any type of exhaust fan must be checked for
adequate combustion air when all of these devices are
in operation at one time. Sizing of an outside air duct
must be done to meet the requirements of all such devices.

Summary of Contents for 8800 Series

Page 1: ...roperty damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try...

Page 2: ...le efficient operation and long life for which this heating boiler water heater was designed these instructions must be read understood and followed The Series 8800 and 8900 finned copper heating boil...

Page 3: ...mply with this warning may result in a fire causing extensive property damage severe personal injury or death 4 Locate the boiler water heater in an area that will prevent water damage to adjacent con...

Page 4: ...re communicating with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 in2 2000 Btu hr 1100 mm2 kW of the total input rating of all of the equipment in the enclos...

Page 5: ...ollar Failure to comply with this warning can result in severe personal injury or death Always provide a minimum clearance of 6 inches 152 mm between type C vent pipe and any combustible materials Typ...

Page 6: ...e fa or ad quate Remettre les portes et les fen tres les ventilateurs les registres de chemin es et les appareils au gaz leur position originale g Any improper operation of the common venting system s...

Page 7: ...outside of the range listed in Table 5 indicates that the flow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty The maximum allowable flow rate th...

Page 8: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 8 Figure 1 Typical Primary Secondary Piping System Figure 2 Low Temperature Piping...

Page 9: ...8 3 42 4 59 9 34 3 40 8 47 6 54 4 61 6 68 1 75 2 81 7 88 8 95 2 102 4 109 2 116 0 123 1 131 2 157 4 183 6 209 9 236 1 2 2 2 6 3 0 3 4 3 9 4 3 4 7 5 2 5 6 6 0 6 5 6 9 7 3 7 9 8 3 9 9 11 6 13 2 14 9 0 6...

Page 10: ...ed with bronze headers Piping and components connected to the water heater must be suitable for use with potable water The water heater must not be connected to any heating system piping or components...

Page 11: ...er heater inlet must not be less than 110 F 43 C or excessive condensation of the products of combustion will damage the water heater voiding the warranty The method outlined below can be employed to...

Page 12: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 12 Figure 5 Typical Water Heating Piping Figure 6 Multiple Water Heating Piping...

Page 13: ...0 1100 2100 3300 5900 12 000 40 245 500 760 1450 2300 4100 8300 50 215 440 670 1270 2000 3600 7400 60 195 400 610 1150 1850 3250 6800 80 170 350 530 990 1600 2800 5800 100 150 305 460 870 1400 2500 51...

Page 14: ...rol valve to the appliance Do Not interrupt water flow through the boiler water heater En cas de surchauffe ou si l alimentation en gaz ne s arr te pas fermez manuellement le robinet d arr t de l admi...

Page 15: ...6 Wait five 5 minutes to clear out any gas Then small for gas including near the floor If you smell gas STOP Follow B in the safety infomration above If you don t smell gas go to next step 7 Connect...

Page 16: ...ing probe Figure 8 To adjust the pilot the following steps must be taken 1 Remove the pilot gas pressure regulator cap 2 Turn the pressure regulator adjustment screw clock wise to increase the flame a...

Page 17: ...ticipator setting may be necessary if the unit cycles frequently If the room temperature over shoots the thermostat setting reduce the anticipator setting Water Heater Operation Controls The operating...

Page 18: ...Exchanger Replacement 1 Sagging or distorted heat exchanger tubes are an indication of low water flow through the system 2 A damaged heat exchanger must be replaced and the condition that caused the d...

Page 19: ...rn Header 8 Black O Rings 9 Stud Bolts 10 Flange Nuts 11 V Baffle 12 Frame Assembly 13 Main Burner 14 Union 15 Firing Valve 16 Main Gas Valve 17 A Valve 18 Refractory 19 Flue Collector End 20 Down Dra...

Page 20: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 Lower Left Right Jacket End Pnl 72 0016 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 Inlet Outlet Header Cast Iron 01 0001 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Inlet Outlet Header Bronze 01...

Page 21: ...17 19 21 23 25 27 29 31 33 35 Burner Tube Stainless w Bracket 70 0500 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 14 Union 1 53 0054 1 1 1 1 1 1 Union 1 1 4 53 0055 1 1 1 1 1 1 1 Union 1 1 2 53 0056 1 1 15 Firing...

Page 22: ...70 1 70 0371 1 70 0372 1 70 0373 1 70 0374 1 70 0375 1 70 0376 1 70 0377 1 Upper Front Refractory Channel 70 0177 1 70 0178 1 70 0179 1 70 0180 1 70 0181 1 70 0182 1 70 0183 1 70 0184 1 70 0185 1 70 0...

Page 23: ...1 70 0035 1 70 0036 1 70 0037 1 70 0038 1 70 0039 1 70 0040 1 70 0041 1 70 0042 1 70 0043 1 70 0044 1 22 Upper Front Jacket Panel 72 0001 1 72 0002 1 72 0003 1 72 0004 1 72 0005 1 72 0006 1 72 0007 1...

Page 24: ...07 1 72 0008 1 72 0009 1 72 0010 1 72 0011 1 72 0012 1 72 0013 1 72 0014 1 72 0015 1 29 Burner Drawer Side Rail Assy Left 70 0361 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Burner Drawer Side Rail Assy Right 70 03...

Page 25: ...Operator L4008A US only 14 0102 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Operator GIP 9868 CAN only 14 0116 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Operator L6008A 1242 Water Heaters 14 0106 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1...

Page 26: ...1 0154 1 21 0155 1 21 0156 1 21 0157 1 21 0158 1 21 0159 1 21 0160 1 Not Shown Natural to LP Conversion Kit 21 0161 1 2000 to 4500 feet 21 0162 1 21 0163 1 21 0164 1 21 0165 1 21 0166 1 21 0167 1 21 0...

Page 27: ...rn Header 8 Copper Fin Tube 9 Black O Rings 10 Stud Bolts 11 Flange Nuts 12 V Baffle 13 Frame Assembly 14 Main Burner 15 Union 16 Firing Valve 17 Main Gas Valve 18 A Valve 19 Burner Drawer Side 20 Ref...

Page 28: ...0001 32 32 32 32 32 32 10 Stud Inlet Outlet Return Headers 57 0223 24 24 24 24 24 24 11 Nut Inlet Outlet Return Headers 57 0491 24 24 24 24 24 24 12 Heat Exchanger V Baffle 03 1147 15 03 1148 15 03 11...

Page 29: ...nd Refractory Panel Left Right 05 0050 2 2 2 2 2 2 Not Shown Center Refractory Panel 05 0051 4 4 6 8 8 10 20 Corner Refractory Panel 05 0052 4 05 0053 4 05 0054 4 05 0055 4 05 0056 4 05 0057 4 21 Draf...

Page 30: ...1 1 1 Operator L6008G1009 2 Stage 14 0107 1 1 1 1 1 Operator T991E 1018 Modulating Boilers 14 0108 1 1 1 1 1 Operator T991E 1034 Modulating Water Heaters 14 0110 1 1 1 1 1 Operator T6031A 1052 Pool H...

Page 31: ...re between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace S8610 module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused by high or...

Page 32: ...eup valve is open and functioning Remove return header and inspect the heat exchanger tubes Ensure relief valve is properly sized for the system never exceed 160 psi Ensure expansion tank is properly...

Reviews: