43
Item
Application
Description
BOILER 1
ALL
Enables Boiler for operation
BOILER 2
CASCADE
Enables Boiler for cascade operation
BOILER 3
CASCADE
Enables Boiler for cascade operation
BOILER 4
CASCADE
Enables Boiler for cascade operation
IGNITION
ALL
IDLE=no CFH;
PREP=pre-purge or inter-purge between trials for ignition;
IGN=trial for ignition;
BURN=burner operating;
POST=post purge;
HARD=a hard lockout fault has occurred requiring manual reset (Ignition
Lockout or manual high limit); and
SOFT=a soft lockout fault has occurred which interrupts the heating cycle
(any safety other than ignition or manual high limit).
The CFH will resume after the soft lockout fault has been corrected and a
15 min. waiting period has expired.
VENT WALL
ALL
Monitors vent temperature and adjust firing rate if vent temperature
approaches limit for vent material installed/selected.
LIMIT TEMP
ALL
Current Outlet-Limit temperature
EMS Vdc
ALL
Current EMS signal in Volts DC
FIRE RATE
ALL
PIM firing rate
SPEED
ALL
Blower speed in revolutions per minute (rpm)
OUTLET MAX
H Mode 1, 2, 3
Defines Max Outlet temperature offset above Target Setpoint (Press and
hold up and down arrows for 3 seconds to enable adjustment). See VERSA
IC control manual (5000.72).
OPERATOR
ALL
Operator Potentiometer setting on PIM
DIFF
ALL
Current auto differential – Fixed by PIM
Pump Post
ALL
Sets the length of the boiler pump purge
FLAME CUR
ALL
Flame current in micro-amps (µA)
MASS
ALL
Thermal mass recovery see VERSA IC control manual (5000.72).
IDENTITY
ALL
Identifies the unit as boiler, water heater or pool heater
IGN TYPE
ALL
PIM Board type
ID CARD
ALL
Identifies Raypak Identity Card
ERROR CODE
ALL
Current Error Code
ERROR HISTORY
ALL
Up to 15 Error Codes can be logged
Table U. Boiler Menu
4.10.4. Boiler Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well as
software and hardware information