Important:
To avoid potential damage to equipment, ensure voltage selector switch is set to the correct
setting. The clutch voltage may be different from that of the drive itself, for example the range of
both 12 V and 24 V Raymarine drives all have a 12 V clutch. If in doubt, consult your local dealer.
Solenoid (drive) and bypass valve connection - ACU-300
Constant Running Pump (solenoid) drives connect to the connection panel of the ACU-300.
Solenoid drive connection
1.
Electronic steering / jog lever (if required)
2. Back-feed protection diodes (if using an electronic steering or jog lever)
3.
Solenoid out
4.
Solenoid return
5. Solenoid valves (with diodes across spool valves)
Note:
If an electronic steering or jog lever is used, fit diodes (suggested type: 1N4004) in-line with the
solenoid outputs to prevent back-feeding the ACU.
Bypass valve connection and voltage switch
Some drives feature an electrically-operated bypass valve to minimize the effect on the steering
when the autopilot is in standby.
If the drive has a separate bypass valve, connect it to the Bypass connection on the ACU, ensuring
that the voltage selection switch is set correctly to 12 V / 24 V as appropriate.
96
Summary of Contents for Evolution EV-1
Page 2: ......
Page 4: ......
Page 34: ...Item Description Quantity 4 Mounting screws 2 5 Document pack 1 34...
Page 36: ...5 1 Dimensions EV 1 and EV 2 36...
Page 37: ...5 2 Dimensions ACU 100 ACU 150 Product dimensions 37...
Page 38: ...5 3 Dimensions ACU 200 ACU 300 ACU 400 38...
Page 54: ...54...
Page 66: ...66...
Page 80: ...Item Wire color ACU 100 ACU 150 1 Red 2 Blue 3 Green 4 Gray screen 80...
Page 82: ...82...
Page 104: ...104...
Page 114: ...114...
Page 128: ...128...
Page 134: ...134...
Page 138: ......
Page 141: ......