74
Grid Regulation
AS/NZS 4777.2, VDE-AR-N4105, VDE0126-1-1
Safety Regulation
IEC/EN 62109-1&2, IEC62040-1
EMC
EN61000-6-1, EN61000-6-2, EN61000-6-
3, EN61000-6-4,EN61000-4-16, EN61000-
4-18, EN61000-4-29
Table 9.1 Grid specification (single-phase
)
Grid
Specification
Output Voltage
Range (Vac)
Output Frequency
Range (Hz)
Boot wait
time(S)
China
187-252
49.5-50.2
30
Germany
184-264
47.5-51.5
60
Australia-A
180-265
47-52
60
Australia-B
180-265
47-52
60
Australia-C
180-265
45-55
60
Italy(CEI0-21)
195-264
49.8-50.2
60
Italy
(CEI0-21 ACEA)
195-264
49.8-50.2
60
Spain
196-253
48-50.5
180
U.K.
184-264
47-52
180
Hungary
196-253
49-51
300
Belgium
184-264
47.5-51.5
60
W-Australia
180-260
45-52
60
Greece
184-264
49.5-50.5
180
France
184-264
47.5-50.4
60
Bangkok
198-242
49-51
150
Thailand
198-242
47-52
60
S. Africa
180-260
47.0-52
60
50549
184-264
47.5-51.5
60
Brazil
184-264
59.5-60.5
60
0126
184-264
47.5-51.5
60
Ireland
184-264
47-52
180