The E8KT/E10KT/E12KT is naturally ventilated. The location should therefore be clean,
dry and adequately ventilated. The mounting location must allow free access to the unit for
installation and maintenance purposes, and the system panels must not be blocked.
The following locations are not allowed for installation:
⚫
Habitable rooms;
⚫
Ceiling cavities or wall cavities; on roofs that are not specifically considered suitable;
access / exit areas or under stairs / access walkways;
⚫
Where the freezing point can be reached, such as garages, carports or other places
as well as wet rooms (environmental category 2);
⚫
Locations with humidity and condensation over 95%;
⚫
Places where salty and humid air can penetrate;
⚫
Seismic areas - additional security measures are required;
⚫
Sites with altitude over 2000m;
⚫
Places with an explosive atmosphere;
⚫
Locations with direct sunlight or a large change in the ambient temperature;
⚫
Places with flammable materials or gases or an explosive atmosphere.
2.1.2 Restricted Locations
The E8KT/E10KT/E12KT shall not be installed:
1. in restricted locations as defined for panels in AS / NZS 3000;
2. within 600mm of any heat source, such as hot water unit, gas heater, air conditioning
unit or any other appliance.
3. within 600mm of any exit;
4. within 600mm of any window or ventilation opening;
5. within 600mm of side of other device.
A E8KT/E10KT/E12KT installed in any corridor, hallway, lobby or the like and leading to
an emergency exit shall ensure su
ffi
cient clearance for safe egress of at least 1 meter.
The E8KT/E10KT/E12KT must also not be installed in potentially explosive atmospheres
for gas cylinders that are heavier than air gases and have a vent clamp in accordance with
AS / NZS 3000.
2.1.3 Barrier to Habitable Rooms
Summary of Contents for RI-ENERGYFLOW-3P-MODULAR...
Page 4: ...4...
Page 12: ...12 Accessory Cable PACK10 2 Accessory Cable PACK20 4 Accessory Cable PACK30 6...
Page 13: ...13 Accessory Cable PACK40 8...
Page 14: ...14...
Page 28: ...28 Figure 17 Wiring the Communication Cable...
Page 30: ...30 Figure 19 PV Wiring Step12 Close the lid and tighten the screw Figure 20...
Page 58: ...58...