4
Raychem-IM-H58033-XLTracePipeFreezeProtectionCOM-EN 18/01
2
Installation Guidelines
2.1
heating Cable Storage
• Store the heating cable in a clean, dry location.
Temperature range: 0°F (–18°C) to 140°F (60°C).
• Protect the heating cable from mechanical
damage.
2.2
Pre-Installation Checks
Check materials received
Catalog number: 5, 8 or 12 XL
—
1 or 2 -CR -CT
Power output (W/ft)
Product family
Voltage 1 = 120 Vac (only available for 5 or 8)
2 = 208–277 Vac (available for 5, 8, or 12)
Jacket type: Polyolefin or
Fluoropolymer
(Required for grease and fuel lines)
Figure 1: Xl-Trace catalog number
• Review the heating cable design and compare the
list of materials to the catalog numbers of the
heating cables and connection kits received to
confirm that the proper materials are on site. The
heating cable type is printed on its jacket.
• Ensure that the service voltage available is correct
for the XL-Trace heating cable selection.
• Inspect the heating cable and connection kits to
ensure there is no in-transit damage.
• Verify the system design does not exceed the max-
imum exposure temperature of the heating cable
5XL/8XL: 150°F (65°C) 12XL: 185°F (85°C)
• Verify that the heating cable jackets are not dam-
aged by conducting the insulation resistance test
(refer to Section 7) on each reel of heating cable.
Do not power the heating cable when it’s on the
reel.