![Raychem XL-Trace Installation And Operation Manual Download Page 35](http://html.mh-extra.com/html/raychem/xl-trace/xl-trace_installation-and-operation-manual_789561035.webp)
31
Raychem-IM-H58033-XLTracePipeFreezeProtectionCOM-EN 18/01
5
Control, monitoring and Power
Distribution
TaBle 8: COnTrOl SySTemS
Description
electronic thermostats
EC-TS
The Raychem EC-TS is an ambient or line-
sensing electronic thermostat housed in a
NEMA 4X enclosure with 2 x 1/2 in conduit
entries for power and 1 gland entry for the
sensor. The temperature set point and LED
indicators for alarm, power, and heating
cable status can be visually checked through
the clear lid. Electrical rating is 30 A at 100–
277 V, 50–60 Hz, SPST switch. The EC-TS
includes a 25 ft (7.6 m) sensor.
ECW-GF
ECW-GF-DP
The Raychem ECW-GF is an ambient or line-
sensing electronic controller with 30-mA
ground-fault protection. The controller can
be programmed to maintain temperatures up
to 200°F (93°C) at voltages from 100 to 277
V and can switch current up to 30 Amperes.
The ECW-GF is complete with a 25-ft (7.6-
m) temperature sensor and is housed in a
NEMA 4X rated enclosure. The controller
features an AC/DC dry alarm contact relay.
An optional ground-fault display panel (ECW-
GF-DP) can be added to provide ground-fault
or alarm indication in applications where
the controller is mounted in inaccessible
locations.
electronic controllers and sensors
C910-485
The Raychem C910-485 is a compact, full-
featured, microprocessor-based, single-point
commercial heating cable control system
with integrated equipment ground-fault
protection. The C910-485 provides control
and monitoring of electric heating cable
circuits for commercial heating applica-
tions. The C910-485 can be set to monitor
and alarm for high and low temperature,
low current, and ground-fault level. The
C910-485 includes a communication module
to remotely configure, control and monitor
the heating cable circuits through a building
management system (BMS).