Installation and Inspection
Record
Installation and Inspection record
Facility
Test Date:
Circuit number:
Heating cable type:
Controllers:
Temperature setting:
Circuit length:
Commission
Inspection date:
Visual inspection
Confirm 30-mA ground-fault device (proper rating/function)
Visual inspection inside connection boxes for overheating, corrosion,
moisture, and other problems.
Proper electrical connection, ground, and bus wires insulated over
full length
Damaged or missing thermal insulation; damaged, missing, cracked
lagging or weatherproofing.
Covered end seals, splices, and tees properly labeled on insulation.
Check controllers for moisture, corrosion, setpoint, switch operation.
Insulation resistance test
m-Ohms
Bus to braid (Test A)
500 Vdc
1000 Vdc
2500 Vdc
Braid to pipe (Test B)
500 Vdc
1000 Vdc
2500 Vdc
Circuit length verification
Capacitance test: Circuit length (ft) = Capacitance (nF) x
Capacitance factor (x 3.28 = m)
Power check
Circuit voltage
Panel
(Vac)
Circuit amps after 2 hours
(Amps)
Pipe temperature
(°F) (°C)
Power = (volts x amps after 2 hrs) / circuit length (watts/ft) (watts/m)