24
Raychem-IM-H58033-XLTracePipeFreezeProtectionCOM-EN 18/01
2
Installation Guidelines
TaBle 6: aCCeSSOrIeS FOr general BUrIeD PIPIng
Catalog
number
Description
Standard
pkg
ETL
“Electric Traced” label (use 1
label per 10 feet of pipe)
10 labels
GT-66
Glass cloth adhesive tape for
attaching heating cable to pipe at
40°F (4°C) or above. See Table 7.
66 ft
GS-54
Glass cloth adhesive tape for
attaching heating cable to pipe
above –40°F (–40°C). See Table 7.
54 ft
AT-180
Aluminum tape. Required for
attaching heating cable to plastic
pipe (use 1 foot of tape per foot of
heating cable).
180 ft
RayClic-SB-02 Wall mounting bracket
1
TaBle 7: QUanTITy OF glaSS ClOTh aDheSIVe TaPe
reQUIreD (aTTaCh aT 1-FOOT InTerValS)
Pipe size (in)
<2
3
4
6
8
10
Feet of pipe per GT-66
roll
60
50
40
25
20
15
Feet of pipe per GS-54
roll
49
41
33
20
16
12