I N S T A L L A T I O N
1.
The installation must be done by a qualified and licenced electrician
according the local legislation.
2.
The electrical installation must be free of power during the entire
installation period.
3.
Since this Charging Unit uses circuits that reference to ground, no
Megging must be done after connecting to power.
4.
Wiring and protection:
Version
Wiring *
Mains Circuit Breaker
(MCB)
Residual Current Device
(RCD)
16A / 1 Phase
3G2,50mm
2
30mA, Type A
16A / 3 Phase
5G2,50mm
2
30mA, Type
32A / 1 Phase
3G6,00mm
2
30mA, Type A
32A / 3 Phase
5G6,00mm
2
*
For cable length upto 25m
PLEASE NOTE:
All charges include an AC (> 30mA) and
DC (> 6mA) residual-current-detection.
Always place a type A RCD and the MCB (or
combination unit) in the electrical cabinet.
5.
Open bottom cover of the Charge Station
(5 screws – see picture). Carefully brake out
required cable opening for incoming power cable
and charge cable.
power cable from the back. Use supplied M25
6.
Use 4 wood screws M4,5x35mm to mount Charging Station on the wall.
The Charging Station should be installed between 0,80m and 1,20m from
bottom to the ground.
HOME BOX PLUS / Version: EV045
3. SETUP I-MAX
SETUP
<- I-MAX ->
Here you can set the maximum charging current.
You can choose between 7A and 32A with steps of 2A.
To make your choice please use the left or right arrow
button. To confirm press the middle button.
4. READOUT -> ERR MEMORY
SETUP
<- ERR MEMORY ->
Confirm with the middle button to enter the error memory
screen. You can see max. 10 error codes.
With the left and right arrow buttons you can scroll to the
last code. To return into the setup menu please press the
middle button. In case of error message please contact
Ratio Electric for support.
5. I-CAL -> CALIBRATION
SETUP
<- I-CAL ->
The calibration has already been done.
It is possible to calibrate the charger only once.