Figure 16: µA Bar Graph Meter Display
Figure 17: Display “High Voltage On” Time
Figure 18: Lockout Jumper Location
NOTE
current causing decreased transfer efficiency. If high
output, check maintenance of applicator and external
equipment of the power supply.
Some lockouts are sealed using sealant
to prevent them from being modified for
safety reasons. These lockouts should
ONLY
be modified by Ransburg Authorized
Representatives.
Measuring “High Voltage On” Time
The 9060 High Voltage Controller records the amount
of time the high voltage is triggered on up to 99,999
hours. This value is display on the kV and µA displays
of the unit. There are two registers that retain this
information, one that may be reset, the other that is
permanently retained in memory. The number of hours
the unit’s high voltage has been on may be displayed
by depressing at the same time the preset 1 and reset
buttons (See Figure 17). The display will show hours
of use for 3 seconds. This is the resettable register.
To reset this register, press the reset button while the
hours are displayed.
To view the non-resettable register, press the preset 2
and reset buttons at the same time. This display will
show the hours for 3 seconds.
LOCKOUTS
There are lockouts that may be done at the PC board
(see Figure 18). These lockouts may be used individ-
ually or in combination as required. If the jumpers are
disconnected, the original functions are re-enabled.
After changing any jumpers, the AC power must cycled
for the new setting to take affect.
Front Panel Lockout
This feature locks out any changes to the kV setting
from the front panel of the Controller.
1. Set the kV to the desired value using the front pan-
el buttons. This must be set prior to installing the
jumper.
2. Turn AC power off and access the interior of the
Controller.
3. Place the jumper across the two (2) pins at location
16 on the main PC board (See Figure 19).
4. Close the Controller and turn AC power back on.
Pressing the front panel +, -, or setpoint buttons will
now have no affect on the kV setting.
µA BAR GRAPH
METER
PRESS AND
HOLD BOTH FOR
RESETTABLE ON
TIME REGISTER
PRESS AND HOLD BOTH
FOR NON-RESETTABLE
ON TIME REGISTER
DISPLAY OF “HV ON” TIME IN HOURS
CP-17-02
21
9060 Classic High Voltage Controller -
OPERATION