AREA
Tells where hazards
may occur.
HAZARD
Tells what the hazard is.
SAFEGUARDS
Tells how to avoid the hazard.
Improper or inadequate
operation and maintenance
procedures will cause a
fire hazard.
Protection against inadvertent
arcing that is capable of
causing fire or explosion is lost
if any safety interlocks are
disabled during operation.
Frequent Power Supply or
Controller shutdown indicates
a problem in the system
requiring correction.
Electrostatic arcing must be prevented. Safe
sparking distance must be maintained between
the parts being coated and the applicator. A
distance of 1 inch for every 10KV of output voltage
is required at all times.
Unless specifically approved for use in hazardous
locations, all electrical equipment must be located
outside
Class I or II, Division 1 or 2 hazardous
areas, in accordance with NFPA-33.
Test only in areas free of flammable or combustible
materials.
The current overload sensitivity (if equipped)
MUST be set as described in the corresponding
section of the equipment manual. Protection
against inadvertent arcing that is capable
of causing fire or explosion is lost if the current
overload sensitivity is not properly set.
Frequent power supply shutdown indicates a
problem in the system which requires correction.
Always turn the control panel power off prior
to flushing, cleaning, or working on spray
system equipment.
Before turning high voltage on, make sure no
objects are within the safe sparking distance.
Ensure that the control panel is interlocked
with the ventilation system and conveyor in
accordance with NFPA-33, EN 50176.
Have fire extinguishing equipment readily
available and tested periodically.
Improper operation or
maintenance may create
a hazard.
Personnel must be properly
trained in the use of this
equipment.
Personnel must be given training in accordance
with the requirements of NFPA-33, EN 60079-0.
Instructions and safety precautions must be read
and understood prior to using this equipment.
Comply with appropriate local, state, and national
codes governing ventilation, fire protection,
operation maintenance, and housekeeping.
Reference OSHA, NFPA-33, EN Norms and
your insurance company requirements.
General Use and
Maintenance
Spray Area
Explosion Hazard
CP-17-02
3
9060 Classic High Voltage Controller -
SAFETY