Page 17
WES+ Installation and Operations Manual V2.3 Ramtech Electronics 2017
Now select
Communication
from the Menu.
On the next menu select
GSM-Status.
Wait a short time for the unit
to find a signal. If the unit fails to find a signal - go back to the
beginning and start the process again.
In case of any problem with the sim card, cello tape the reaming
packaging to the back of your unit (as shown below).
Your unit is now ready to use.
Final Testing
Step
No.
Action
Pass criteria
Notes
1.
Hold unit flat on workbench.
Hold button “A” and press ‘B’
three times in quick succession
Red, Amber and Green LEDs simultameously flash
three times.
Amber LED then flashes in groups of 3
Brings unit out of “Transit’ mode.
If amber LED flashes in groups of 4 then
ensure back tamper is held down firmly
and wait for 10 seconds or until flashes
are in groups of three.
2.
Hold “A” button down on both
units. Release buttons when
LEDs units illuminate green.
Amber LEDs on both units illuminate, then turn to
green.
This pairs the units with the fire point to
test the radio communication and
confirms that the internal tamper is not
active.
3.
Intermittent flashing green LED
Green LED flashes once every four seconds
Indicates no fault warnings are active.
4.
Press the manual call point on
captive test fire point
Check that unit sounds and strobe flashes, or display
and captive fire point strobe flashes
Alarm has been raised by the unit and
a message has been sent via radio to
captive fire point.
5
Reset manual call point
Amber LED will flash in groups of 5, within 5 seconds
of call point reset.
Units in re-arm mode
6.
Stand unit up (to release back
tamper), then hold ‘A:’ and press
“B” three in quick succession.
Red, Amber and Green LEDs simultaneously illumi-
nate and then extinguish
Unit in transit mode
SIG
Low Signal
Unit NNN has a low radio signal
Yes
TST
Silent Test
Unit NNN initiated a Silent Test
Yes