WES+ Installation and Operations Manual V2.3 Ramtech Electronics 2017
It is not possible to exit the warning screen until all warnings have
either been resolved or acknowledged by an authorised user.
To acknowledge a warning, select it with the navigation pad and press
enter. You will need to enter your access code for the first warning you
acknowledge.
Base Station Controls
The navigation pad, shown below, is used to move between menus,
change characters and select entries.
Menu items can be selected using the up and down arrows and then
pressing enter (middle arrow button).
Change characters using the up and down arrows while the character
is highlighted.
WES Warning Code Guide
Warning Code
Warning
Description
Self-Cleaning
SMS setting
BAT
Low Battery
Unit NNN has a low battery
No
5
DET
Detector Tamper
Detector unit NNN has had its detector head
removed
Yes
3
EXT
External Tamper
Unit NNN has been removed from the wall/
ceiling
Yes
4
FLT
Flat
Unit NNN has turned off, its battery is flat
No
8
INT
Internal Tamper
Unit NNN has been opened up and potentially
tampered with or damaged
No
2
LAT
Latched
The call point on unit NNN is still latched in
after the alarm has been reset
Yes
10
REM
Removed
Unit NNN has been deactivated and removed
from the fire alarm system
No
9
SIG
Low Signal
Unit NNN has a low radio signal
Yes
6
TST
Silent Test
Unit NNN initiated a Silent Test
Yes
7
Scroll through characters by holding down the up or down arrows.
Move to the next character or field using the right arrow.
Use the left arrow button to move to a previous character.
To exit a menu, move to the left-most character and press the left
arrow key again.
Home Screen
Pressing enter on the home screen opens the main menu, giving
access to the System Log Menu and the Settings Menu. The settings
are only available to authorised users with an access code.
If the base station has not yet been paired, it will display ‘Unpaired’
instead of the site name.