MANUALE ISTRUZIONI / INSTRUCTIONS MANUAL
MTR605/025/DASM - R605/027/DASM - R605/170/DASM
Modello/Model R605DASM
I/ 15
sistema_
elettronico
_60
5_CAN.fm
(*) random variation of these parameters could make the CAN-BUS inaccessible.
(**)legal values are:
0 = 500 Kbit/sec
1 = 250 Kbit/sec
2= NOT VALID
3 = 125 Kbit/sec
The control may be given in two ways: read only or setting.
An example of the read only is:
Base_id<cr>
The value of of this parameter will be viewed.
Or:
Base_id = 0x540
The value of this parameter will be varied. An inexistent or wrong control will return an
Invalid command response. Wrong parameters could return an Invalid value response.
These parameters are permanently memorized in the microprocessor FLASH memory
and are retained even on powering down.
The FLASH memory has a finite number of operations consequently these settings are
advisable only when strictly necessary. Values set beyond the limits indicated will not
be memorised.
When setting is terminated, power down the board, remove the connections. On start
up, the board will operate with the new settings.
Warning!
The optional bit related to the LCD display may be set at zero only also in versions
designed for LCD display operation. Should a fork photocell type OPB840W51 need to
be connected (J3), proceed as follows:
Pin 1
not connected
Pin 2
not connected
Pin 3
black
Pin 4
red
Pin 5
white
Pin 6
green
Resetting to 1 may be performed only in the factory.
Warning!