background image

3

Valve Output Wiring

The controller transformer provides 26.5 VAC output for
the station valves. The output leads are color coded and
stamped with the corresponding station designations.
(See Figure 3.)

1.

 A 

1

/

8

" dia. hole is provided in the bottom of the cabinet

for connection of a 

3

/

4

" conduit fitting.

2.

 Connect one Lead from EACH valve to the desired

STATION OUTPUT lead using wire nuts. On “C” units,
connect one Lead from each valve to the desired station
output screw on the terminal strip.

NOTE:

 

A maximum of four Rain Bird, 2 watt, solenoid

valves may be connected to each station output lead.
This applies when the Master Valve circuit is NOT used.
Refer to Figure 4 for variations of the station load capac-
ities.

3.

 Connect the second lead from all valves to the white

COMMON output lead. On “C” units, connect the second
lead from each valve to a “COMMON” wire and connect
that wire to a screw labeled “COM” on the terminal strip.
Record the valve locations or landscape zone identifica-
tion for each station on the label inside the cabinet door.

MOUNTING

1.

 Choose a location that provides a minimum clearance of 13" wide x 10" high. Since

the electrical connections are provided at the bottom of the cabinet, clearance should
be allowed for the conduit connections  etc. (Refer to Figure 2.)

2.

 Remove the 4 panel mounting screws, carefully lift out the panel and disconnect the

wire harness at the connectors.

3.

 Position the cabinet on the wall at the mounting location, and with a pencil, mark

the 3 mounting hole locations on the wall. Two vertical holes are provided for mount-
ing to a wall stud.

4. 

 Install the two top fasteners first. (

Note: 

Use #10 screws).

5. 

 Install the bottom fastener, and tighten all screws. With the cabinet mounted se-

curely to the wall, proceed with the wiring connections.

ELECTRICAL CONNECTIONS

ALL WIRING MUST BE INSTALLED AND CONNECTED IN ACCORDANCE WITH
LOCAL CODES. A basic wiring diagram, with color code identification is provided on
the inside surface of the cabinet for easy reference.

RC-7A
OUTPUT LEAD

COLOR
CODE

Station 1........... Brown

2........... Red
3........... Orange
4........... Yellow
5........... Green
6........... Blue
7........... Violet

Master Valve.......... Black

Valve Common......... White

Figure 3.

VALVE OUTPUT IDENTIFICATION

NUMBER OF VALVES

PER STATION

TYPE OF
MASTER VALVE

2.0
WATT
Solenoid

None...............

2 Watt Solenoid........

4
3

Figure 4.

STATION CAPACITY

Summary of Contents for RC-1260C

Page 1: ...AL with 14 SCHEDULING PINS The calendar DAY dial contains 14 cap tive pins for scheduling irrigation everyday or any day within a two week range Each pin represents a 24 hour period beginning at midnight Embossed characters are on the dial adjacent to each day of the week C STATION SELECTOR INDICATOR DIAL The STATION selector indicator dial contains the timing controls for each of the stations The...

Page 2: ...ill struggling with your old sprinkler timer Having a hard time complying with local watering restrictions Upgrading to a new Rain Bird sprinkler timer is easier than you might think New timers are easier to program than ever before with powerful features to help save you time and water while keeping your yard healthy and vibrant There are lots of models to meet your needs including indoor and out...

Page 3: ...liminates controller output to the system valves without interrupting the clock operation F CIRCUIT BREAKER RESET BUTTON Circuit overload reset button F A built in circuit breaker protects the controller from damage due to current overload Push to reset after the source of trouble has been remedied G CURRENT STATION INDICATOR STATION indicator G identifies the current position of controller operat...

Page 4: ...NTING 1 Choose a location that provides a minimum clearance of 13 wide x 10 high Since the electrical connections are provided at the bottom of the cabinet clearance should be allowed for the conduit connections etc Refer to Figure 2 2 Remove the 4 panel mounting screws carefully lift out the panel and disconnect the wire harness at the connectors 3 Position the cabinet on the wall at the mounting...

Page 5: ...ection with a 1 2 conduit fitting 3 Connect a 120 Volt A C supply line to the LINE INPUT leads Main Power Wiring RC 7C RC 4C RC 1260C The 120 VAC step down transformer is mounted in the lower left hand comer of the controller cabinet A 1 2 14 NPSM conduit nipple extends through the cabinet bottom for connection to a conduit housing junction box or other approved attachment Make the electrical conn...

Page 6: ...rve each circuit for proper operation Upon satisfactory checkout of the system proceed to adjust the controller clock CAUTION Dead Heading a pump running the pump s motor without water flowing through it may cause pump damage It may also result in personal injury from hot water spraying from the pump as a result of static water within the pump heating to a temperature where plastic pipe and fittin...

Page 7: ... pin s corresponding to the day s on which watering is desired Re member each DAY pin represents a 24 hour period beginning at midnight 2 Next select the desired starting time s and push in the corresponding pin s on the HOUR dial Multiple starts within a given day may be scheduled after completion of the time accumulated by the previous cycle see NOTE following Step 3 3 The first mark square dot ...

Page 8: ...ll operate for the time set on the dial after which the remaining stations will follow in sequence until the REST position again ap pears under the Station pointer RAIN SHUTDOWN There may be occasions where it is desired to interrupt all landscape irrigation Condi tions such as rainy weather system repair landscape renovation or other excavation work The temporary shutdown of the system is accompl...

Page 9: ...Insufficient cycle time al lowed b Total cycle time coincides with a succeeding START pin a Adjust cycle time for more than 15 minutes b Reset the HOUR pins or readjust the accumulated cycle time Some stations do not op erate a Station time set at OFF b Faulty valve wiring a Set TIME control for more than 3 minutes b Check connections be tween controller and valves Also check valve actuators Stati...

Reviews: