2
D. STATION TIME CONTROL
KNOBS:
Individual TIME controls for each station.
Timing is adjustable from 3 to 60 minutes (6 to 60 minutes in the RC 1260C) to suit all
landscape growth requirements. A small white arrow moves with each knob along the
timing scale on the Station dial (C) for visual indication of the time setting. The scale is
marked-off in 5 minute graduations and the ratchet action of the knob provides for pre-
cision adjustment with each "notch" representing one minute increments. The OFF po-
sition eliminates the station from the watering schedule. All omitted stations are auto-
matically “rapid advanced” through, to the next timed station.
E. OPERATIONAL MODE
SWITCH:
The 2-position MODE switch (E) provides the
operating control for the system. AUTO position for automatic irrigation as scheduled
and "timed" watering of manually selected station. The OFF position is used for rainy
weather shutdown. This position eliminates controller "output" to the system valves
without
interrupting the clock operation.
F. CIRCUIT BREAKER RESET BUTTON:
Circuit overload reset button (F). A built-in
circuit breaker protects the controller from damage due to current overload. Push to
reset after the source of trouble has been remedied.
G. CURRENT STATION
INDICATOR:
STATION indicator (G) identifies the current
position of controller operation.
H. CURRENT TIME INDICATOR:
TIME indicator (H) identifies the current time on the
controller clock.
I. CURRENT DAY INDICATOR:
DAY indicator (I) identifies the current day of the wa-
tering schedule.
INSTALLATION
The RC Series controller’s cabinet is suitable for wall mounting in sheltered areas.
Three mounting holes are provided through the back surface of the cabinet. Before
mounting the controller, consideration must be given as to accessibility, electrical
power source and connections to the system control valves.
11”
6”
3”
6
3
/
4
”
9
3
/
4
”
5
/
8
”
7
/
8
” DIA. INPUT
1
3
/
4
”
CONTROLLER
OUTLINE
MOUNTING
HOLES
DOOR OPENS
TO LEFT
DOOR
1
1
/
8
” DIA.
OUTPUT
CONNECTION
Figure 2
CONTROLLER MOUNTING
2
1
/
4
”
7”
MINIMUM 6” FOR
ELECTRICAL
CONNECTIONS