Protect the top of the chimney with the chimney cap against the rain and winds. The
distance from the cap to the chimney is 200mm.
The chimney should come up in comparison to a roof according to suggestions in the
picture (
Picture 11
). If some taller objects are close to a chimney, consider that and
additionally increase the height.
The chimney has to have a condensation drain port, as well as one inspection door.
The door should always be sealed well during the operation.
Situation 2:
In this situation, the smoke pipe has to go at least 1.5m vertically up in the room with
the boiler and then burst through a wall and to be connected to the chimney.
The smoke pipe has to have the condensation T-piece where it exits the boiler as well
as the possibility to be disassembled in order to be cleaned.
WARNING: Not following the rules while setting up smoke channels and the
chimney, may lead to improper operation of the boiler, and endanger human
health and even their lives. The greatest danger is from poisonous gases which
are the products of combustion. In these situations, where the smoke pipe and
chimney, as well as the air supply, aren’t executed according to the manual,
Radiator inzenjering can’t take any responsibility for the unwanted
consequences.