7.3.2. Changing the dosing time of the transporter in the operating mode
The menu for modifying this running time and combustion speed of the doser. 10
calibration levels are available, 5 for increasing, and 5 for decreasing, the 0 value corresponds
to factory settings. Changes in this menu directly impact the power of recipe combustion in the
Run Mode and Modulation. For each settings’ step, value increases or decreases for the
percentual value P15 that can be adjusted in the hidden menu. This menu is visible only if P11
differs from 1.
Example: P15=10%, Step=-1
Default
values
CO3=2,0 CO4=3,0
CO5=4,0
CO6=5,0
CO7=6,0
C11=1,0
Calibrated values
CO3
=1,8
CO4
=2,7
CO5
=3,6
CO6
=4,5
CO7
=5,4
C11
=0,9
Table 4. Changing the dosing time of the conveyor in the operating mode
The calculated values belong to the range defined by parameters P27 and P05.
Picture 27. Changing the dosing time of the screw transporter
7.3.3. Changing the power of the fan in the running mode
The system has 10 calibration systems. Changes in this mode impact the current recipe
and operational power in the Run Mode and Modulation. For each settings’ step, value
increases or decreases for the percentual value P16 that can be adjusted in the hidden menu.
This menu is visible only if P11 differs from 1. How to change is displayed in the picture.
Example: P16=5%, Step=+3
Default
values
UO3=1000 UO4=1200 UO5=1400 UO6=1600 UO7=1800 U11=900
Calibrated
values
UO3
=1150
UO4
=1380
UO5
=1610
UO6
=1840
UO7
=2070
U11
=1030
Table 5. Changing the fan power in operating mode