R2K 24 - RAD - ING - Inst.Manual - 2002.1_CSA
2. FIRST START-UP
SUPPOR
T CENTER
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P10
DOMESTIC FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN DOMESTIC MODE. [SEE 2.1.6 ‘COMBUSTION BLOWER
FREQUENCY/HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
45 - VALUE
SET
FOR
PA R A ME T E R
P11
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P11
DOMESTIC FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE IN
DOMESTIC MODE [SEE 2.1.6 ‘COMBUSTION BLOWER FREQUENCY/
HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
V A L U E
SET
FOR
PA R A ME T E R
P10 - 203
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P12
HEATING FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE IN
HEATING MODE. [SEE 2.1.6 ‘COMBUSTION BLOWER FREQUENCY/
HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
45 - VALUE
SET
FOR
PA R A ME T E R
P13
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P13
HEATING FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE IN
HEATING MODE [SEE 2.1.6 ‘COMBUSTION BLOWER FREQUENCY/
HEAT CAPACITY DIAGRAM’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
V A L U E
SET
FOR
PA R A ME T E R
P12 - 203
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P14
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED
DURING START-UP.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02).
V A L U E
SET
FOR
PA R A ME T E R
P10 - 203
THE VALUE IS EXPRESSED IN
HERTZ (1HZ = 30 RPM) - (PRE-
SET AT 120 HZ)