9

1143923-W2-E

2.

  For stud partitions alternative fixings may be 

required. 

3.

  Isolating valves 

must

 be installed close to the 

Mixer for ease of maintenance.

4.

  Pipework must be rigidly supported and avoid 

any strain on the connections.

5.

  Pipework dead-legs should be kept to a 

minimum.

6.

  Decide on a suitable position for the Mixer. 

The position of the Mixer and the Shower 

Fittings must provide a minimum gap of 25 mm 

between the spill-over level of the shower tray/

bath and the showerhead (refer to illustration). 

This is to prevent back-siphonage. For further 

information on the installation of your 

Shower 

Fittings

, refer to the Fittings Installation and 

User Guide.

 

Note!

 Only use Shower Fittings recommended 

by the manufacturer or supplier.

 

Note!

The thermostatic mixing valve will be 

installed in such a position that maintenance of 

the TMV and its valves and the commissioning 

and testing of the TMV can be undertaken.

Suitable Plumbing Systems

Gravity Fed:

The thermostatic mixer must be fed from a cold 

water cistern (usually located in the loft space) and 

a hot water cylinder (usually located in the airing 

cupboard) providing nominally equal pressures.

Mains Pressurised Instantaneous Hot Water 

System (Combination Boiler):

The thermostatic mixer can be installed with 

systems of this type with balanced pressures. 

(Recommended Minimum Maintained Pressure: 

1.0 Bar

).

Note!

 On combination boiler systems we 

recommend that the thermostatic mixer is 

operated in the maximum flow position in order to 

achieve the minimum flow rate required to ignite 

and run the boiler. 

Unvented Mains Pressure System:

The thermostatic mixer can be installed with an 

unvented, stored hot water system.

Pumped System:

The thermostatic mixer can be installed with an 

inlet pump (twin impeller). The pump must be 

installed in a suitable location and in accordance 

with its instructions.

General

Installation must be carried out in accordance 

with these instructions, and must be conducted by 

designated, qualified and competent personnel.

The installation must comply with the “Water 

Supply (Water Fittings) Regulations or Scottish 

Byelaws” or any particular regulations and 

practices, specified by the local water company 

or water undertakers.

Note!

 Make sure that all site requirements 

correspond to the information given in section: 

‘Specifications’

. For Type 2 Valves see also 

supply conditions in the TMV2 Requirements 

Manual.

1. 

The Mixer must not be installed in an area 

where it may freeze.

Hose Retaining Ring

25 mm 

Spill Over 

Level

INSTALLATION

Summary of Contents for V10

Page 1: ...1143923 W2 E PRODUCT MANUAL V10 THERMOSTATIC SHOWER VALVE IMPORTANT Installer This Manual is the property of the customer and must be retained with the product for maintenance and operational purpose...

Page 2: ...y water fittings Regulations 1999 The approved designations for Type 2 Valves are as follows Key High Pressure HP Low Pressure LP Models Designation Rada V10 LP S HP S HP SE The economy designation is...

Page 3: ...instructions 2 Retain this guide for later use 3 Pass on this guide in the event of change of ownership of the installation site 4 Follow all warnings cautions and instructions contained in this guid...

Page 4: ...alve q 1 x Rada V10 Exposed Shower Valve q 2 x Concealing Plates q 2 x Compression Nuts q 2 x Olives q 2 x Wall Plugs q 2 x Fixing Screws q 1 x 2 5 mm Hexagonal Key q 1 x Flow Regulator 6 l min q 1 x...

Page 5: ...m Hexagonal Key q 1 x Concealing Plate Assembly Rada V10 Concealed Shower Valve q 1 x Rada V10 Concealed Shower Valve q 1 x Flow Regulator 6 l min q 1 x Flow Regulator 9 l min refer to section Flow Re...

Page 6: ...q 2 x Fixing Screws q 1 x VR145 Showerhead q 1 x 3 mm Hexagonal Key q 1 x 2 5 mm Hexagonal Key q 1 x O Key q 2 x Wall Plugs q 2 x Fixing Screws q 1 x O Seal q 1 x Hole Plug q 1 x Flow Regulator 6 l m...

Page 7: ...V10 Concealed Shower Valve Rada V10 Exposed Shower Valve Rada V10 Contract Pack 121 115 69 18 5 24 5 750 40 15 5 15 103 183 56 76 39 59 21 20 Building In Depth 50 36 5 115 126 54 19 30 50 46 76 5 41...

Page 8: ...utlet Flow l min Outlet Flow l min 9l m Outlet Flow l min No Flow Regulators Pressure Loss bar Outlet Flow l min 9l m Outlet Flow l m Outlet Flow l min 6l m Outlet Flow l min No Flow Regulators Temper...

Page 9: ...Mains Pressurised Instantaneous Hot Water System Combination Boiler The thermostatic mixer can be installed with systems of this type with balanced pressures Recommended Minimum Maintained Pressure 1...

Page 10: ...V10 Exposed n a 6 L Min Black Supplied in the component pack designed to be fitted in the shower valve outlet Rada V10 Concealed n a 6 L Min Black Supplied in the component pack designed to be fitted...

Page 11: ...ll at 110 mm centres Note If you are retro fitting your mixing valve onto existing pipework an Adjustable Elbow Pack is available if required refer to section Accessories 39 mm 3 For solid walls drill...

Page 12: ...shed through before connection to the mixer Failure to do so may result in product malfunction and will not be covered under the guarantee 11 Fit the compression nuts and olives onto the pipework 12 A...

Page 13: ...is to prevent the flexible hose from obstructing the shower controls refer to illustration 5 Mark the routes for the hot and cold supply pipework at 103 mm centres Hot Left Cold Right Note If it is n...

Page 14: ...8 Carefully cut away the plasterboard and or brick work to a depth of between 56 and 76 mm from the finished wall surface Important Take care to stay within the marked out diameter otherwise the conc...

Page 15: ...rom the pipes before proceeding 16 For solid wall installations or stud partition installations without rear access go to instruction 21 For stud partition installations with access to the rear of the...

Page 16: ...all surface and should be fitted with the cutout in line with the outlet Installation 1 Draw a centre line between the inlet pipework and using the adjustable backplate as a template mark the position...

Page 17: ...osition and type of flow regulator will vary by model For high pressure systems above 0 5 bar identify your model and install the flow regulator as illustrated where appropriate For gravity fed or oth...

Page 18: ...er 3 Loosen the control lever grubscrew with the 2 5 mm hexagon key supplied and pull off the control lever 4 Unscrew the hub retaining screw with a 2 5 mm hexagon key Note Do not remove the hub 5 Ins...

Page 19: ...ws retaining the valve on to the backplate If you require a Rada trained service engineer or agent refer to section Customer Services Fault Diagnosis Symptom Only hot or cold water from the mixer outl...

Page 20: ...ter Note If the filter is damaged it must be replaced 7 Install the filters and reconnect the valve and fittings reverse of the above procedure 8 Turn on the water supplies and check for any leaks Con...

Page 21: ...nts identified B 1663 162 Screw Pack components identified C 1663 168 Pipe Concealing Plate Adjustable Elbow V10 Contract 1663 335 Seal Pack components identified D 1663 167 Adjustable Elbow Assembly...

Page 22: ...ied B 1663 162 Screw Pack components identified C 1663 189 Component Pack components identified D 1663 155 Filter Pack x2 1663 187 Backplate Assembly B C D 1663 188 Elbow Filter Pack x2 1663 186 Conce...

Page 23: ...kit 1 25 m flexible hose clamp bracket assembly hose retaining ring and adjustable spray handset Available in chrome finish Suitable for connection to Exposed shower controls Rada Rigid Riser 1 1651...

Page 24: ...product is us or our appointed representative Routine maintenance or replacement parts to comply with the requirements of the TMV2 or TMV3 healthcare schemes Accidental or wilful damage Products purc...

Reviews: