Check blend circuit flow rate.
Flow rate is less than 19 l/m. Reset circuit
flow rate and check for the following:
•
Air locks
•
Blocked strainers
•
Closed valves
•
Pump failure
Checkvalves
Check circuit to make sure checkvalves are
correct positioned and operating normally.
(See
Recirculation Circuit - Plumbing
Schematic
)
Check mixed return temperature.
Minimum recirculation loop temperature
loss = 1°C
Water pressure
Make sure supply pressures are balanced.
Make sure mixed return is flowing correctly
to hot water supply inlet. Check for the
following:
•
Air locks
•
Blocked strainers
•
Closed valves