62
Stop Valve
Full Bore Isolating Valve
Pressure Reducing Valve
Shower
Thermometer
Cold Water
Hot Water
Mixed Water
Check Valve
Recirculation Pump
Key
Strainer / Filter
Needle Valve
Flow indicator
Safety Valve
Water
Heater
Temp High 53˚C
Setpoint 49˚C
Temp Low 38˚C
Setpoint 49˚C
Temp High
Error Temp
49˚C
Problem:
“LCD Display shows any of the following...”
Blend circuit /
'DRV Programming
Software'
Blend circuit does not fully return to normal
temperature within the
'Disinfection
Timeout'
period. Check the following:
•
Disinfection Timeout value.
•
Cool Down start and finish times.
•
Early abort of disinfection cycle.
•
Use of a dump valve to speed up cool
down time.
dump valve
position