32

Change installation settings

Caution: 

These settings should only be carried out by the installer as they may affect the safety and function of the heating system

H

INSTALLER 
SETTINGS

Customise the controller according application needs (by installer only)

default settings
( ) = value range

0 Code

Enter Code (= 7) in order to access the menus. It is valid for 1 Hour

1 Application

This controller is suitable for the heating system mentioned on right column

FLOOR see 1.

10

Set temperature 
to read

Show set temperature instead of room temperature

NO

12

Number for 
floor tempe-
rature

Read the floor temperature as number.
Instead of a temperature in °C a number will be displayed e.g. instead of 28,5 °C, 285 can be 
read.

0.0 
(-5,0 ... +5,0)

13 Backlight

Continuously OFF or temporarily illuminates after key press. 

SHORT (SHORT, 
OFF)

14 Language

Select preferred operating language

15 Info

Displays Controller-type and -version.

16

Reset user 
settings only

Only USER SETTINGS will be set to factory settings. The energy counter will not be re-set; 
to do this see H9).

NO

Summary of Contents for QuickTherm HF

Page 1: ...QuickTherm HF Room Thermostat QuickTherm HF Room Thermostat Smart Operating and installation instructions GB...

Page 2: ...Controller 2 Select application Press OK Press OK Select Application ROOM LIMITER FLOOR FLOOR is factory pre set Press OK Note In case of changing the application the user and Installer settings will...

Page 3: ...he internal or remote sensor The Heater will be switched on when the temperature drops below the current set point Actual Day Actual Room Temperature Calling for Heat Blinks if detached from power mod...

Page 4: ...steresis configurable for ON OFF control Valve protection Heating or Cooling can be selected Adaptation to valves normally open or normally closed Measures the room temperature with the internal senso...

Page 5: ...ing in plastic wall boxes only To insert or remove a flexible wire press pin The plastic tab must be in place to pro vide insulation between the terminals wires and the mounting screw Connecting accor...

Page 6: ...es for example inside a conduit Connecting the remote sensor Caution The sensor is at mains voltage 6 Technical Data Order Type QuickTherm HF Room Thermostat Smart Supply voltage 230 V AC 50 HZ 195 25...

Page 7: ...orage 20 C 70 C without condensation Rated impulse voltage 4 kV Ball pressure test 75 2 C Voltage and Current for the purposes of Interference measurements 230 V 0 1 A Degree of protection IP 30 Prote...

Page 8: ...08 Caution Maximum length of removed cable insulation 8 mm Remote sensor 7 Wiring Diagram Dimensions 7 8...

Page 9: ...ion there will be no need to change the time temperature settings on the device To select another program see 9 G1 Programm 1 Events 1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 21...

Page 10: ...1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 21 0 18 0 21 0 18 0 21 0 15 0 Events 1 2 Time 7 00 23 00 22 00 Temperature C 21 0 15 0 Monday to Friday Saturday and Sunday 23 00 22 0...

Page 11: ...for Saturday Programm 3 Events 1 2 3 4 Time 6 00 8 30 17 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Events 1 2 3 4 Time 7 00 10 00 12 00 23 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Monday to Friday...

Page 12: ...rectly b Is the Optimum Start feature switched on see H7 Did the controller have enough time several days to adapt to the room s characteristics c Is an automatic change between Summer and Winter time...

Page 13: ...ller to application needs see main menu INSTALLER SETTINGS Set a constant temperature manual operation see main menu MAN Use a separate program for special days see main menu AT HOME Keys to confirm a...

Page 14: ...0h of the first day it ends at 24h of the last day In the period of time before HOL starts AUTO will be active While waiting for holiday start date other mode can be selected AUTO MAN TIMER HOME INFO...

Page 15: ...s on power Display reading OFF Frost protection may happen if selected See H6 Switching ON again by activating e g NO 5 Summer Winter time change over Select if automatic Summer Winter Time changeover...

Page 16: ...d on right column It can be selected if a remote sensor has to be used ROOM NO see 1 10 Set temperature to read Show set temperature instead of room temperature NO 11 Adjust Temperature Adjust tempera...

Page 17: ...eizungsart H1 RAUM Frostschutz H6 NO kann nicht aktiviert werden Optimum Start H7 NO kann nicht aktiviert werden Heating Heating Cooling im Falle eines Fehlers Relais Aus Temperaturen SchaltzeitenvonH...

Page 18: ...plug display unit switch off and on power supply Temperature Resistance Temperature Resistance 10 C 66 8 k 30 C 26 3 k 20 C 41 3 k 40 C 17 0 k 25 C 33 0 k 50 C 11 3 k In case of errors Err is blinkin...

Page 19: ...The heater will be switched on when the temperature drops below the current set point Actual Day Actual Floor Temperature Calling for Heat Blinks if detached from power module or there is no mains po...

Page 20: ...s week month year Energy cost per hour configurable Frost protection Range limits for adjusting max and min temperature Access protection Operating language can be selected Control mode PWM or ON OFF...

Page 21: ...ing in plastic wall boxes only To insert or remove a flexible wire press pin The plastic tab must be in place to pro vide insulation between the terminals wires and the mounting screw Connecting accor...

Page 22: ...power cables for example inside a conduit Connecting the remote sensor Caution The sensor is at mains voltage 6 Technical Data Order Type QuickTherm HF Room Thermostat Smart Supply voltage 230 V AC 50...

Page 23: ...impulse voltage 4 kV Ball pressure test 75 2 C Voltage and Current for the purposes of Interference measurements 230 V 0 1 A Degree of protection IP 30 Protection class of housing II see Caution Pollu...

Page 24: ...programs There are 3 pre set time temperature programs in the controller Pre set program 1 as shown below is the default Therefore if pre set program 1 is the best program to suit the application ther...

Page 25: ...Programm 1 Events 1 2 3 4 Time 6 00 8 00 19 00 22 00 Temperature C 28 0 18 0 21 0 15 0 Events 1 2 3 4 Time 8 00 10 00 17 00 22 00 Temperature C 28 0 18 0 21 0 15 0 Monday to Friday Saturday and Sunda...

Page 26: ...5 6 Time 6 00 8 00 12 00 14 00 19 00 22 00 Temperature C 28 0 18 0 28 0 18 0 28 0 15 0 Events 1 2 3 4 5 6 Time 8 00 10 00 12 00 14 00 19 00 22 00 Temperature C 28 0 18 0 28 0 18 0 28 0 15 0 Monday to...

Page 27: ...27 Programm 3 Events 1 2 4 Time 11 00 13 00 22 00 Temperature C 21 0 18 0 15 0 Events 1 2 3 4 Time 8 00 10 00 19 00 22 00 Temperature C 21 0 18 0 28 0 15 0 Monday to Friday Saturday and Sunday...

Page 28: ...rectly b Is the Optimum Start feature switched on see H7 Did the controller have enough time several days to adapt to the room s characteristics c Is an automatic change between Summer and Winter time...

Page 29: ...ller to application needs see main menu INSTALLER SETTINGS Set a constant temperature manual operation see main menu MAN Use a separate program for special days see main menu AT HOME Keys to confirm a...

Page 30: ...starts at 0h of the first day it ends at 24h of the last day In the period of time before HOL starts AUTO will be active While waiting for holiday start date other mode can be selected AUTO MAN TIMER...

Page 31: ...on power Display reading OFF Frost protection may happen if selected See H6 Switching ON again by activating e g NO 5 Summer Winter time change over Select if automatic Summer Winter Time changeover Y...

Page 32: ...tem mentioned on right column FLOOR see 1 10 Set temperature to read Show set temperature instead of room temperature NO 12 Number for floor tempe rature Read the floor temperature as number Instead o...

Page 33: ...the relay to be On or Off PWM 10 10 30 OFF OFF 0 1 5 0 10 Min 1 30 6 Frost protection Set frost protection temperature Only if controller is switched OFF the temperature will be controlled to that va...

Page 34: ...power unit fails unplug and re plug display unit switch off and on power supply Temperature Resistance Temperature Resistance 10 C 66 8 k 30 C 26 3 k 20 C 41 3 k 40 C 17 0 k 25 C 33 0 k 50 C 11 3 k In...

Page 35: ...ated if the floor temp drops below the set min value This is even when the room temp is too high In case of function Max FloorTemp H3 heating will be stopped if the floor temp exceeds the set max valu...

Page 36: ...teresis configurable for ON OFF control Min and max limits for floor temperature adjustable Valve protection Adaptation to valves normally open or normally closed Adjustable heating interrupt accordin...

Page 37: ...ing in plastic wall boxes only To insert or remove a flexible wire press pin The plastic tab must be in place to pro vide insulation between the terminals wires and the mounting screw Connecting accor...

Page 38: ...e power cables for example inside a conduit Connecting the remote sensor Caution The sensor is at mains voltage 6 Technical Data Order Type QuickTherm HF Room Thermostat Smart Supply voltage 230 V AC...

Page 39: ...rage 20 C 70 C without condensation Rated impulse voltage 4 kV Ball pressure test 75 2 C Voltage and Current for the purposes of Interference measurements 230 V 0 1 A Degree of protection IP 30 Protec...

Page 40: ...40 Caution Maximum length of removed cable insulation 8 mm Remote sensor 7 Wiring Diagram Dimensions 7 8...

Page 41: ...ion there will be no need to change the time temperature settings on the device To select another program see 9 G1 Programm 1 Events 1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 28...

Page 42: ...1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 21 0 18 0 21 0 18 0 21 0 15 0 Events 1 2 Time 7 00 23 00 22 00 Temperature C 28 0 15 0 Monday to Friday Saturday and Sunday 23 00 22 0...

Page 43: ...1 2 3 4 Time 06 00 08 30 17 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Events 1 2 3 4 Time 7 00 10 00 12 00 23 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Monday to Friday Saturday and Sunday 23 00 22...

Page 44: ...o adapt to the room s characteristics c Is an automatic change between Summer and Winter time activated see G5 2 The controller does not accept any changes Is access protection switched on see G6 3 Th...

Page 45: ...ller to application needs see main menu INSTALLER SETTINGS Set a constant temperature manual operation see main menu MAN Use a separate program for special days see main menu AT HOME Keys to confirm a...

Page 46: ...starts at 0h of the first day it ends at 24h of the last day In the period of time before HOL starts AUTO will be active While waiting for holiday start date other mode can be selected AUTO MAN TIMER...

Page 47: ...on power Display reading OFF Frost protection may happen if selected See H6 Switching ON again by activating e g NO 5 Summer Winter time change over Select if automatic Summer Winter Time changeover Y...

Page 48: ...ng systems For ON OFF you can select Hysteresis OFF no temperature hysteresis even at very low changes of temp the relay will switch over according to the Min On OffTime setting Min On OffTime the min...

Page 49: ...ctivated for the specified time each day at 10 00 h in the morning 6 Frost protection Set frost protection temperature Only if controller is switched OFF the temperature will be controlled to that val...

Page 50: ...power unit fails unplug and re plug display unit switch off and on power supply Temperature Resistance Temperature Resistance 10 C 66 8 k 30 C 26 3 k 20 C 41 3 k 40 C 17 0 k 25 C 33 0 k 50 C 11 3 k In...