Q-Controller System Operation Manual
- 19 -
86550-001-000 Rev B
Sensor RS-485 Port
Baudrate:
Baud Rate for the 4x RS-485 Port at TB11 to TB14 remote device
network
OptoMux protocol, default 4800bps
Modbus RS-485 Port
Baudrate:
Baud Rate for RS-485 Port for Modbus protocol, the Q-Controller
responds as a Modbus slave using RTU protocol.
Default is 19200 bps.
Modbus RS-485
Parity:
The parity bit can be set to “EVEN”, “ODD” and “No Parity”.
Default is “No Parity”.
Modbus Slave
Address:
The assigned address is the Q-Controller as a slave device in
Modbus protocol. Range 1 to 247.
Default is 214.
Hush Period Timer:
When a hush button or hush style switch is pressed to silence
Buzzer/Horn and buzzer style relays, the timer is active at the
same time. When the timer is timeout, the hush button will be
expired and will not silence the buzzer/horn and relays any more.
If the alarm is still present, the buzzer/horn and relays will be
actuated again. Expired switch needs to manually reset (push
again) in order to function again.
Default is 5 minutes
Reset Relay Period
Timer:
When a reset style switch is pressed to manually reset its
assigned relays, the relays will be overridden to reset, the timer is
active at the same time. When the timer is timeout, the switch
input will be expired and the relays will not be overridden any
more. If the alarm is still present, the relays will actuate again.
Expired switch input needs to manually reset in order to function
again.
Default is 5 minutes
Exit:
Save settings and Return to previous menu