5.3.11
AO (Analog Output) Setup
Click AO-Box list item will enter below configuration screen.
AO-Box
Description
Enable/Disable
Q-Controller only monitor and control enabled devices
Description
Description for this channel of AO-Box
Convert Mode
•
Average Mode
•
Peak Mode
Analog outputs may work with sensors and analog inputs. It’s
allowed to assign more than one input per output channel. The
inputs could be averaged or taken the peak among the inputs as
the value to convert output current.
Reading at 4mA
Assign a concentration for both the 4.0 milliamp signal, and the
20 milliamp signal. You may assign a larger concentration for 4.0
milliamps than for 20 milliamps; the Q-Controller will still
stretch a straight line signal between the two points.
Reading at 20mA
See above
Assigned Input
Define which inputs assigned to the AO channel