QUATRO
HU315
32
QUATRO
-------------------------------------------------------------------------------------
”We Make Clean Air”
30 Hymus Boulevard, Montreal, Quebec, H9R 1C9 Tel.: (514) 630-4444 Fax: (514) 630-4454 website: www.quatro-air.com
solution as for the steam cylinder and a soft brush.
•
Drain pan
:
Clean the pan of any mineral deposits and check that the water flows freely from the pan to the drain at the
drain valve.
•
Supply, fill, overflow pipes
:
Check that these are clear and clean or replace if necessary.
IMPORTANT WARNING:
after having
replaced
or checked the plumbing, check that
components have been reconnected
correctly
with the proper seals. Re-start the
humidifier
and perform a number of supply and
drain
cycles (from 2 to 4), then check for
any water
leaks.
Replacement Parts
Three Phase Humidifiers
HU315 Part #’s
Water Parts
Fill Cup + Conductivity Meter
18C453A008
Fill Valve Kit
KITVC00012
Drain Valve Kit
13C499A030
Internal Pipe Kit
UEKT00000M
Conductivity Probe:
208-230V
18C431A004
Disposable Cylinders:200/230 Vac 3~,
Conductivity 350/1250 µS/cm
H525
Electrical Parts
Contactors
0203001AXX
Power Transformers:
208-24 Vac
09C476A027
Fuse Holders
0606192AXX
Fuses 1,2:
208-230V
0605319AXX
Electrical Parts
Led Display Ver. C-P
UEKDP00000
Control Module Ver. H-T
UEH0000001
Control Board Ver. C-P **
UEP0000001
Control Board Ver. H-T
UEI0000000
Flat Connection Cable
59C460A003
HU315 Three Phase Humidifier