Alarms
In the event of an alarm, the alarm LED (9) will flash, the alarm relay will close, and the alarm code will flash in
the display. Multiple alarms will flash in sequence, alternating with the main display. Pressing the PRG button
will reset the alarms, although still active alarms will continue to display.
Controller
Causes
Solution
Action Reset
display
Alarm
relay
Reset
relay
H
H
EH
Over-current at the
electrodes; probable
electrode malfunction
or water conductivity
temporarily too high
(especially when
starting after a short
stop)
1. Check the operation of the
drain valve
2. Check for fill valve leakage
3. Drain part of the water and
re-start
Shut-
down
N/A
Active
N/A
EL
Power not available;
no steam production
when on
1. With the machine off and
disconnected from the main
power, check the internal
electrical connections
Shut-
down
N/A
Active
N/A
EC
High supply water
conductivity
1. Check limit set for b6
2. Turn the machine off and
clean the water conductivity
probes
3. If the problem persists,
change the source of supply
water or install a suitable
treatment system
(demineralization, even
partial).
Note: the problem will not be
resolved by softening the
supply water.
Shut-
down
N/A
Active
N/A
EP
Excessive reduction in
output
1. Cylinder completely spent
or water with excessive foam.
Perform maintenance on the
cylinder.
Shut-
down
Manual Active Manual
EF
Lack of water
1. Check that the fill pipe from
the main to the humidifier and
the internal pipe are not
blocked or bent and that there
is sufficient pressure (0.1-0.8
mpa, 1-8 bar)
2. Check the operation of the
fill valve
3. Check that the steam outlet
is not working against
excessive back-pressure,
preventing the flow of water
into the cylinder by gravity
4. Check that the steam outlet
pipe is not is kinked and that
there are no sags.
Shut-
down
Automatic
when
water
returns
Active
Automatic
when
water
returns