QUATRO
HU315
30
QUATRO
-------------------------------------------------------------------------------------
”We Make Clean Air”
30 Hymus Boulevard, Montreal, Quebec, H9R 1C9 Tel.: (514) 630-4444 Fax: (514) 630-4454 website: www.quatro-air.com
Resetting Factory Defaults
If errors have occurred when setting the parameters, the controller may be reset to the factory default values:
•
in the first 5 seconds from start-up (while the three dashes are displayed), press the PRG button (2) until
the upper dash in the center flashes (1);
•
release the PRG button within 3 seconds to confirm the permanent reset of the factory defaults; to confirm
the reset, the upper dash will stay on for 2 seconds;
•
the factory reset is not carried out if the PRG button is pressed for more than 3 seconds, until the upper
dash disappears.
Recalling the default parameters does not change the parameter relating to the unit of measure (A1), and it is
thus recommended to check and if necessary select and save the unit of measure as required, and then recall
the default parameters. In this way the default values will automatically be converted.
Maintenance
Periodic checks
•
After one hour of operation:
For both disposable and cleanable cylinders, check that there are no
significant water leaks.
•
Every fifteen days or no more than 300 operating hours:
For both disposable and openable
cylinders check operation, that there are no significant water leaks and the general condition of the
cylinder. Check that during operation there is no arcing between the electrodes.
•
Every three months or no more than 1000 operating hours:
For disposable cylinders, check
operation, that there are no significant water leaks and, if necessary, replace the cylinder; for cleanable
cylinders, check that there are no blackened parts of the cylinder. If there are blackened parts of the
cylinder, check the condition of the electrodes, and if necessary replace them together with the o-rings
and the cover gasket.
•
Annually or no more than 2500 operating hours:
For disposable cylinders, replace the cylinder; for
cleanable cylinders check operation, that there are no significant water leaks, the general conditions of
the cylinder, check that there are no blackened parts of the cylinder: if this is the case, check the
condition of the electrodes, and if necessary replace them together with the o-rings and the cover
gasket.
•
After five years or no more than 10,000 operating hours:
For both disposable and openable
cylinders, replace the cylinder. After extended use or alternatively when using water with a high salt
content, the solid deposits that naturally form on the electrodes may reach the stage where they also
stick to the inside wall of the cylinder; in the event of especially conductive deposits, the consequent
heat produced may overheat the plastic and melt it, and, in more severe cases, puncture the cylinder,