ATL P1000 Series Library Unpacking Instructions
Document 6221100-02, Ver. 2, Rel. 0
March 1999
6
Selecting an Installation Location
Figure 4 shows the floor space requirements for the rack-mount P1000.
Figure 4 Floor Space
Requirements,
Rack-mount Library
Floor Clearance
4
The stand-alone P1000 has a floor clearance of 0.75 in. (1.9 cm). Place
the library on a level, uncarpeted floor free of defects.
Floor Strength and
Inclination
4
The floor at the installation site must be rated at 250 lb/ft
2
(1221 kg/
m
2
). This is sufficient to support a fully loaded P1000 on the floor or in
a rack.
The floor at the installation site must be level to within 0.25 in (6.4 mm)
over a 6 ft by 6 ft (1.8 m by 1.8 m) area.
Overhead Clearance
4
To remove the P1000 enclosure, there must be a minimum clearance of
24 in. (61 cm) above the library. When combined with the height of the
library (21 in./53 cm), this is a total of 45 in. (114.5 cm) from the floor
(stand-alone library) or bottom of the slide (rack-mount library).
Power and Grounding
4
The library auto-ranging power supply accepts single-phase, 90 VAC
to 264 VAC input power at 47 Hz to 63 Hz.
30 in. (76.2 cm)
17.5 in.
(45 cm)
24 in. (61 cm)
19-inch rack
Library
(extended
from rack)
24 in.
(61 cm)
each side
24 in.
(61 cm)
Back
Front