Addendum B
Bypassing a malfunctioning Soft-start Module.
In the event that the soft-start module fails, it may be bypassed by plugging the cord for the 220
volt receptacle on the control panel directly into the 220 feed from the transformer. Procedure
is outlined below.
Step 1;
Remove the main fuse and place the heavy black cable over the back of the cabinet out
of the way. Disconnect the inverter main power cable.
Step 2;
Pick up the power board and lay it partially out of the cabinet as shown on the top
photo on page 24. This allows access to the 220 volt system power cords.
Step 3;
Disconnect the power feed line from the control panel's 220 volt outlet from the socket
from the soft-start module. (Red circle) Disconnect the cord from the 220 volt supply box.
(Green circle), now, connect the cord from the control panel directly into the 220 volt supply
box. Replace the power board and main fuse.
37