SECTION 5 – TECHNICAL DATA
QUANTECH
42
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
Excessive flow will cause damage to the
cooler. Do not exceed max. cooler flow.
Special care should be taken when mul-
tiple chillers are fed by a single pump.
TABLE 4 -
VOLTAGE LIMITATIONS
UNIT POWER
MIN.
MAX.
200-3-60
180
220
208-3-60
187
229
230-3-60
200
254
380-3-60
342
402
460-3-60
414
508
575-3-60
520
635